13010 Oil pressure, coolant temp, fuel level input

No. Setting Range Factory

setting

Description

13010 Oil pressure

input

Set point Multi-in 102

Multi-input 105

Multi-input 108

Auto detection

EIC oil pressure

Auto

detection

13011

Cool water

input

Set point

Multi-in 102

Multi-input 105

Multi-input 108

Auto detection

EIC oil pressure

Auto

detection

13012

Fuel level

input

Set point

Multi-in 102

Multi-input 105

Multi-input 108

Auto detection

EIC oil pressure

Auto

detection

3.8.4 AC average

The following menus define the data used for the AC average page in the utility software. Note that these menus are only available

in the utility software.

14000 Average generator over-voltage L-L 1

No. Setting Range Factory

setting

Description

14001 Avg. G U> L-L

1

Set point 100.0 to 120.0 % 103.0 %

14002

Avg. G U> L-L

1

Timer 0.1 to 100.0 s 10.0 s

14003

Avg. G U> L-L

1

Relay output A

Not used

Option dependent

Not used

14004

Avg. G U> L-L

1

Relay output B

Not used

Option dependent

Not used

14005

Avg. G U> L-L

1

Enable

OFF

ON

OFF

14006

Avg. G U> L-L

1

Fail class F1 to F9 F2 (Warning)

14010 Average generator over-voltage L-L 2

No. Setting Range Factory

setting

Description

14011 Avg. G U> L-L

2

Set point 100.0 to 120.0 % 105.0 %

14012

Avg. G U> L-L

2

Timer 0.1 to 100.0 s 5.0 s

14013

Avg. G U> L-L

2

Relay output A

Not used

Option dependent

Not used

14014

Avg. G U> L-L

2

Relay output B

Not used

Option dependent

Not used

PARAMETER LIST 4189340688R EN Page 181 of 222