10800 RMI 1 type

No. Setting Range Factory

setting

Description

10800 RMI type 1 Type Sensor type 1

Sensor type 2

Sensor type 3

Configurable RMI

Sensor type 1

10810 to 10960 Configurable RMI 108 curve

No. Setting Range Factory

setting

Description

10810 RMI 1 input

set point 1

10820 RMI 1 output

set point 1

10830 RMI 1 input

set point 2

10840 RMI 1 output

set point 2

10850 RMI 1 input

set point 3

10860 RMI 1 output

set point 3

10870 RMI 1 input

set point 4

10880 RMI 1 output

set point 4

10890 RMI 1 input

set point 5

10900 RMI 1 output

set point 5

10910 RMI 1 input

set point 6

10920 RMI 1 output

set point 6

10930 RMI 1 input

set point 7

10940 RMI 1 output

set point 7

10950 RMI 1 input

set point 8

10960 RMI 1 output

set point 8

Set point 0 to 1800 Ω 10 Ω

Set point -49 to 482 40

Set point 0 to 1800 Ω 44.9 Ω

Set point -49 to 482 50

Set point 0 to 1800 Ω 81 Ω

Set point -49 to 482 60

Set point 0 to 1800 Ω 134.7 Ω

Set point -49 to 482 80

Set point 0 to 1800 Ω 184 Ω

Set point -49 to 482 100

Set point 0 to 1800 Ω 200 Ω

Set point -49 to 482 110

Set point 0 to 1800 Ω 210 Ω

Set point -49 to 482 115

Set point 0 to 1800 Ω 220 Ω

Set point -49 to 482 120

PARAMETER LIST 4189340688R EN Page 176 of 222