3.7.2 RMI 105

NOTE

RMI 105 settings are only accessible in the utility software.

10630 RMI 1 type

No. Setting Range Factory

setting

Description

10630 RMI type 1 Type Sensor type 1

Sensor type 2

Sensor type 3

Configurable RMI

Sensor type 1

10640 to 10790 Configurable RMI 105 curve

No. Setting Range Factory

setting

Description

10640 RMI 1 input

set point 1

10650 RMI 1 output

set point 1

10660 RMI 1 input

set point 2

10670 RMI 1 output

set point 2

10680 RMI 1 input

set point 3

10690 RMI 1 output

set point 3

10700 RMI 1 input

set point 4

10710 RMI 1 output

set point 4

10720 RMI 1 input

set point 5

10730 RMI 1 output

set point 5

10740 RMI 1 input

set point 6

10750 RMI 1 output

set point 6

10760 RMI 1 input

set point 7

10770 RMI 1 output

set point 7

10780 RMI 1 input

set point 8

10790 RMI 1 output

set point 8

Set point 0 to 1800 Ω 10 Ω

Set point -49 to 482 40

Set point 0 to 1800 Ω 44.9 Ω

Set point -49 to 482 50

Set point 0 to 1800 Ω 81 Ω

Set point -49 to 482 60

Set point 0 to 1800 Ω 134.7 Ω

Set point -49 to 482 80

Set point 0 to 1800 Ω 184 Ω

Set point -49 to 482 100

Set point 0 to 1800 Ω 200 Ω

Set point -49 to 482 110

Set point 0 to 1800 Ω 210 Ω

Set point -49 to 482 115

Set point 0 to 1800 Ω 220 Ω

Set point -49 to 482 120

3.7.3 RMI 108

NOTE

RMI 108 settings are only accessible in the utility software.