3.6 External communication setup

3.6.1 CAN port setup

7840 CAN select

No. Setting Range Factory setting Description

7841

7842

7843

7844

CAN A

CAN B

CAN C

CAN D

0, 2, 3, 6

0, 2, 3, 6

0, 1, 3, 11

0, 1, 3, 11

PMS Primary

PMS Secondary

Off

Off

0. Off

1. External I/O

2. PMS Primary*

3. EIC

6. PMS Secondary*

11. Ext. modules DEIF

7845 CAN E 0, 1, 3, 11 EIC

7846 CAN F 0, 1, 3, 11 Off

*Requires option G4, G5 or G8.

3.6.2 Modbus/Profibus communication

7500 Communication control (requires option H2 or H3)

No. Setting Range Factory

setting

Description

7501 Comm.

control

7502

7503

Comm.

control

Comm.

control

Power

Frequency

Voltage

OFF

ON

OFF

ON

OFF

ON

OFF

OFF

OFF

These settings must be ON if

commands are to be sent via

Modbus communication. When

enabled, the Modbus values

will overrule external and

internal settings.

7504

7505

Comm.

control

Comm.

control

Cos phi

Reactive power

OFF

ON

OFF

ON

OFF

OFF

Voltage, power factor and

reactive power control requires

AVR control (option D1).

7510 External communication (requires option H2 or H3)

No. Setting Range Factory

setting

Description

7511 Ext.

communicatio

n

ID 1 to 247 1 The mode ASCII is used for

modem communication (ASCII:

7 data bit, RTU: 8 data bit).

7512

Ext.

communicatio

n

Baud rate

9600

19200

9600

7513

Ext.

communicatio

n

Mode

RTU

ASCII

RTU

3.6.3 External I/O communication setup

7890 CIO configuration

No. Setting Range Factory

setting

Description

7891 CIO enable OFF

ON

OFF

Enabling CIO communication.