3.5.6 Power management internal communication
7530 Internal communication ID
No. Setting Range Factory
setting
Description
7531 Int. comm. ID ID 1 to 32 1
3.5.7 Ground relay
8120 Ground relay (requires option G4, G5 or G8)
No. Setting Range Factory
setting
8121 Ground relay Output A Not used (option
dependent)
8122 Ground relay Output B
8123 Ground relay Enable
Not used (option
dependent)
OFF
ON
8124 Ground relay Timer 1 to 30 s 1 s
Not used
Not used
8125 Ground relay Fail class F1 to F9 F3 (Trip GB)
OFF
Description
Selection of relay output for
start point grounding
(parameters 8121 and 8122).
Parameter 8123 is used to
enable the ground relay
feature. The timer setting is for
how long a ground relay
feedback failure is accepted.
8126 Ground relay Type
Continuous
Pulse
Continuous
8130 Ground relay position (requires option G4, G5 or G8)
No. Setting Range Factory
setting
Description
8131 Gnd open fail Timer 1 to 30 s 1 s Alarms related to the position
8132 Gnd open fail Fail class F1 to F9 F3 (Trip GB)
of the ground failure breaker.
8133 Gnd close fail Timer 1 to 30 s 1 s
8134 Gnd close fail Fail class 1 to 30 s F1 (Block)
8135 Gnd pos fail Timer 1 to 30 s 1 s
8136 Gnd pos fail Fail class F1 to F9 F3 (Trip GB)
8150 Ground relay control settings (requires option G4, G5 or G8)
No. Setting Range Factory
setting
Description
8151 Gnd close
condition
Configuration
Hz/V OK
RPM MPU level
RPM EIC level
Start active
Hz/V OK
Configuration for closing and
opening of the ground relay.
8152
Gnd open
condition
Configuration
After cooldown
After extended stop
After
cooldown
8153
Gnd close
RPM
Configuration 0 to 4000 RPM 1000 RPM
PARAMETER LIST 4189340688R EN Page 171 of 222