8880 Load-dependent start/stop calculation (requires option G4, G5 or G8)
No. Setting Range Factory
setting
Description
8881 Start/stop
calc.
8882
Start/stop
calc.
S1
S2
kW
kVA
Value
Percentage
kW
Value
These settings are used to
decide how the load-dependent
start and stop commands in the
power management system
should be calculated.
INFO
Parameter group 8170 is outdated. Use the load-dependent start-stop timers for fuel optimisation.
3.5.4 Priority selection
8030 Priority selection (requires option G4, G5 or G8)
No. Setting Range Factory
setting
Description
8031 Priority select. Priority Manual abs.
Running hours abs.
Fuel optimisation
Manual rel.
Running hours rel.
Fuel optimization +
Running hours
Manual abs.
Setup of priorities.
8080 Priority 1 to 5 (requires option G4, G5 or G8)
No. Setting Range Factory
setting
Description
8081 Priority 1 ID 1 to 32 1 Parameter 8086 is only
8082 Priority 2 ID 1 to 32 2
applicable if Manual is selected
in parameter 8031.
8083 Priority 3 ID 1 to 32 3
Parameter 8086 resets itself to
8084 Priority 4 ID 1 to 32 4
OFF automatically once the
new settings have been
8085 Priority 5 ID 1 to 32 5
transmitted.
8086
Transmit new
priority
Enable
OFF
Manual update
Running hour update
OFF
8090 Priority 6 to 11 (requires option G4, G5 or G8)
No. Setting Range Factory
setting
Description
8091 Priority 6 ID 1 to 32 6
8092 Priority 7 ID 1 to 32 7
8093 Priority 8 ID 1 to 32 8
8094 Priority 9 ID 1 to 32 9
8095 Priority 10 ID 1 to 32 10
8096 Priority 11 ID 1 to 32 11
PARAMETER LIST 4189340688R EN Page 169 of 222