8010 Load-dependent stop (requires option G4, G5 or G8)

No. Setting Range Factory

setting

Description

8011 Load dep.

stop

8012

8013

Load dep.

stop

Load dep.

stop

P set point

S set point

1 to 20,000 kW

1 to 20,000 kVA

200 kW

200 kVA

Parameter 8015 set to ON will

block the load dependent stop

if a heavy consumer (from a

controller running older

software) is connected.

% set point 1 to 100 % 70 %

8014

Load dep.

stop

Timer 0.0 to 990.0 s 30.0 s

8015

Load dep.

stop

Select

Blocked OFF

Blocked ON

Blocked ON

8300 Settings for load-dependent start (requires option G4, G5 or G8)

No. Setting Range Factory

setting

Description

8301 Ld. start limit P

2

Set point 1 to 20,000 kW 100 kW

8302

8303

8304

Ld. start limit S

2

Ld. start limit

% 2

Ld. start timer

2

Set point 1 to 20,000 KVA 100 kVA

Set point 1 to 100 % 90 %

Timer 0 to 990 s 10 s

8305

Ld. start timer

2

Set point

OFF

ON

OFF

8310 Settings for load-dependent stop (requires option G4, G5 or G8)

No. Setting Range Factory

setting

Description

8311 Ld. stop limit P

2

Set point 1 to 20,000 kW 200 kW

8312

8313

8314

Ld. stop limit S

2

Ld. stop limit

% 2

Ld. stop timer

2

Set point 1 to 20,000 KVA 200 kVA

Set point 1 to 100 % 70 %

Timer 0 to 990 s 30 s

8315

Ld. stop timer

2

Set point

OFF

ON

OFF

PARAMETER LIST 4189340688R EN Page 168 of 222