3.5.2 Available power

8220 Available power 1 (requires option G4, G5 or G8)

No. Setting Range Factory

setting

Description

8221 Avail. power 1 Set point 10 to 20,000 kW 1000 kW The setting can be used for

8222 Avail. power 1 Timer 1.0 to 999.9 s 10.0 s

conditional connection of load

groups.

8223 Avail. power 1 Relay output A

Not used (option

dependent)

Not used

8224 Avail. power 1 Relay output B

Not used (option

dependent)

Not used

The relay(s) used must be set

to Limit mode.

8225 Avail. power 1 Enable

OFF

ON

OFF

8230 Available power 2 (requires option G4, G5 or G8)

No. Setting Range Factory

setting

Description

8231 Avail. power 2 Set point 10 to 20,000 kW 1000 kW The setting can be used for

8232 Avail. power 2 Timer 2.0 to 999.9 s 10.0 s

conditional connection of load

groups.

8233 Avail. power 2 Relay output A

Not used (option

dependent)

Not used

8234 Avail. power 2 Relay output B

Not used (option

dependent)

Not used

The relay(s) used must be set

to Limit mode.

8235 Avail. power 2 Enable

OFF

ON

OFF

8240 Available power 3 (requires option G4, G5 or G8)

No. Setting Range Factory

setting

Description

8241 Avail. power 3 Set point 10 to 20,000 kW 1000 kW The setting can be used for

8242 Avail. power 3 Timer 3.0 to 999.9 s 10.0 s

conditional connection of load

groups.

8243 Avail. power 3 Relay output A

Not used (option

dependent)

Not used

8244 Avail. power 3 Relay output B

Not used (option

dependent)

Not used

The relay(s) used must be set

to Limit mode.

8245 Avail. power 3 Enable

OFF

ON

OFF

PARAMETER LIST 4189340688R EN Page 166 of 222