8290 Detection of BB measurement failure (requires option G4, G5 or G8)
No. Setting Range Factory
setting
Description
8291 BB meas
failure
8292
8293
8294
BB meas
failure
BB meas
failure
BB meas
failure
Timer 5.0 to 999.9 s 10.0 s If multiple DG controllers are
connected to measure on the
Relay output A
Relay output B
Enable
Not used (option
dependent)
Not used (option
dependent)
OFF
ON
Not used
Not used
ON
same BB, and the BB
measurement on the next
prioritised DG is not available,
this alarm will exclude the
specific DG and start the DG
with next priority.
8295
BB meas
failure
Fail class
F1 to F4
F4 (Trip +
stop)
8921 N+X setup (previously secured mode) (requires option G4, G5 or G8)
No. Setting Range Factory setting Description
8921 N + X setup N + X OFF
N + 1 extra DG
...
N + 8 extra DGs
N + X OFF
Select how much spinning reserve to
connect. For more information, see
Option G4 G5 and G8 Power
management.
8920 Multi-start (requires option G4, G5 or G8)
No. Setting Range Factory setting Description
8922 Multi-start set 1
Auto calculation
Start 1 DG
...
Start 32 DG
Auto calculation
Select the multi-start set points. For
more information, see Option G4 G5
and G8 Power management.
8923 Min. run set 1 0 to 32 1
8924 Multi-start conf
Multi-start set 1
Multi-start set 2
Multi-start set 1
8925
Multi-start set
point 2
Auto calculation
Start 1 DG
...
Start 32 DG
Start 16 DG
8926 Min. run set 2 0 to 32 1
8990 BTB closed ring (requires option G4 or G5)
No. Setting Range Factory
setting
Description
8991 Closed ring Set point
OFF
ON
OFF
This parameter determines
whether it is allowed to close
all BTBs in a ring bus at the
same time.
PARAMETER LIST 4189340688R EN Page 165 of 222