8180 Mains config. (requires option G4, G5 or G8)

No. Setting Range Factory

setting

Description

8181 MB failure

start

Enable

OFF

ON

OFF

Only available in AGC-4

mains.

8182 Parallel Enable

OFF

ON

OFF

8183

No break

transfer

Enable

OFF

ON

OFF

8184 Auto switch Select

8185 Run type Select

OFF

Static section

Dynamic section

All sections

Run all mains

Run one mains

OFF

Run one

mains

8186 Run type ID to run 17 to 32 17

8190 Tie breaker (requires option G4, G5 or G8)

No. Setting Range Factory

setting

Description

8191 Tie breaker TB open point 0 to 20,000 kW 50 kW Only available in AGC-4

8192 Tie breaker Power capacity 1 to 20,000 kW 50 kW

mains.

8193 Tie breaker P. cap. overrule 5.0 to 999.9 s 30.0 s

8194 Tie breaker P. cap. overrule

OFF

ON

OFF

8195 Tie breaker Load time 0.0 to 30.0 s 0.0 s

INFO

Parameter groups 8200, 8210, 8930 and 8940 are outdated. Use an ALC-4 to control heavy consumers.

8270 TB power (requires option G4, G5 or G8)

No. Setting Range Factory

setting

Description

8271 TB power Transducer max. 10 to 20,000 kW 0 kW Only available in AGC-4 mains.

8272 TB power Transducer min. -20,000 kW to 0 kW 0 kW

8273

Deload TB

BSync

Enable

OFF

ON

OFF

If the tie breaker needs to be

deloaded before opening, a

power transducer must be

connected to multi-input 105.

8280 Asymmetric load sharing (requires option G4, G5 or G8)

No. Setting Range Factory

setting

Description

8281 Asymmetric

LS

Set point 1 to 100 % 80 % For more information refer to

the option G4/G5 manual.

8282

Asymmetric

LS

Enable

OFF

ON

OFF

PARAMETER LIST 4189340688R EN Page 164 of 222