3.5 Power management setup

3.5.1 Power management general setup

8020 PM config (requires option G4, G5 or G8)

No. Setting Range Factory

setting

Description

8021 PM config Enable Remote

Local

8022 PM config Update

Update local

Update all

Remote

Update all

Remote and local decide if the

start/stop command of the

plant is given Remote (digital

input) or Local (from the

display).

8023 Easy Connect Enable

OFF

ON

OFF

Update is used to define if the

change of a running mode will

affect all controllers connected

on the power management

CAN line, or only the local unit

where the running mode is

changed.

8110 Running hours (requires option G4, G5 or G8)

No. Setting Range Factory

setting

Description

8111 Running

hours

Priority update 1 to 20.000 hrs 175 hrs If parameter 8113 is ON, the

trip counter in the controller is

reset to 0 hours.

8112

Running

hours

Type

Total

Trip

Load profiled

Total

See Option G4 G5 G8 Power

management for more

information.

8113

Running

hours

Trip counter

OFF

ON

OFF

8140 Stop non-connected DGs (requires option G4, G5 or G8)

No. Setting Range Factory

setting

Description

8141 Stop non-con.

DGs

Delay 10.0 to 600.0 s 60.0 s Stop timer for non-connected

gensets.

PARAMETER LIST 4189340688R EN Page 163 of 222