3.4.7 Power offset

7220 Power offset

No. Setting Range Factory

setting

Description

7221 Power offset

1

Set point -20,000 to 20,000 kW 0 kW Setup of power offset.

7222

Power offset

1

Enable

OFF

ON

OFF

7223

Power offset

2

Set point -20,000 to 20,000 kW 0 kW

7224

Power offset

2

Enable

OFF

ON

OFF

7225

Power offset

3

Set point -20,000 to 20,000 kW 0 kW

7226

Power offset

3

Enable

OFF

ON

OFF

3.4.8 Cos phi offset

7240 Cos phi offset

No. Setting Range Factory

setting

Description

7241 Cos phi offset

1

Set point -0.8 to 0.8 0 Setup of cos phi offset.

7242

Cos phi offset

1

Enable

OFF

ON

OFF

7243

Cos phi offset

2

Set point -0.8 to 0.8 0

7244

Cos phi offset

2

Enable

OFF

ON

OFF

7245

Cos phi offset

3

Set point -0.8 to 0.8 0

7246

Cos phi offset

3

Enable

OFF

ON

OFF

3.4.9 Mains ATS function

7250 Mains ATS

No. Setting Range Factory

setting

Description

7251 Mains ATS Set point 0

1

0 Setup of Mains ATS Function.

0 = ON; 1 = OFF.

7252 Mains ATS Timer 0 to 30 s 0.5 s

3.4.10 Mains transducers

INFO

Scaling (parameter 9030) affects the range and defaults for the following parameters*. The values below are based on

100V-25000V.

PARAMETER LIST 4189340688R EN Page 161 of 222