1190 G/M/BA under-voltage 3

No. Setting Range Factory

setting

Description

1191 G/M/BA U< 3 Set point 40.0 to 100.0 % 95.0 % The alarm and fail class are

1192 G/M/BA U< 3 Timer 0.1 to 100.0 s 5.0 s

activated when the voltage has

been continuously under the

1193 G/M/BA U< 3 Relay output A Not used (option

dependent)

Not used programmed value during the

programmed delay.

1194 G/M/BA U< 3 Relay output B Not used (option

dependent)

1195 G/M/BA U< 3 Enable OFF

ON

Not used

OFF

1196 G/M/BA U< 3 Fail class F1 to F9 F2 (Warning)

1200 Calculation method

No. Setting Range Factory

setting

Description

1201 G/M/BA

voltage trip

1202 BB voltage

trip

Set point

Set point

Ph-Ph

Ph-N

Ph-Ph OR Ph-N

Ph-Ph

Ph-N

Ph-Ph OR Ph-N

Ph-Ph

Ph-Ph

Select phase-phase or phaseneutral

voltage detection.

When phase-phase tripping is

selected, the voltage alarms

relate to the nominal voltage.

When phase-neutral tripping is

selected, the voltage alarms

relate to the nominal voltage

divided by √3.

1203 Unbalance I Set point Ref. to nominal

Ref. to average

Ref. to

nominal

1204 Frequency

trip

Type

L1

L2

L3

L1 or L2 or L3

L1 and L2 and L3

L1 or L2 or L3

Selection of the phase the

controller uses for over-/underfrequency

alarms.

1205 df/dt algorithm Type Standard df/dt

G99 df/dt

Standard df/dt

G99 df/dt is only possible with

option A10.

2.2.4 Frequency protections

Frequency settings relate to the nominal frequency setting.

PARAMETER LIST 4189340688R EN Page 16 of 222