7050 Fixed power settings (Mains controller)

No. Setting Range Factory

setting

Description

7051 Fixed power

settings

7052

7053

7054

Fixed power

settings

Fixed power

settings

Cos phi

reference

Power

Cos phi

0 to 20000 kW

0.10 to 1.00 s

500 kW

0.90

Fixed power parallel with mains

settings. Visibility of these

parameters depends on the

mode selected in parameter

6070.

Cos phi

Cos phi

Inductive

Capacitive

OFF

Fixed for DG(s)

Fixed for imp/exp

Inductive

OFF

For information on how

parameter 7055 works, see

Option A10.

7055

Fixed power

settings

Reference

1 kW : 1 kW

10 kW : 10 kW

100 kW : 100 kW

1000 kW : 1000 kW

1 kW : 1 kW

3.4.4 Mains failure

7060 U Mains Failure

No. Setting Range Factory

setting

Description

7061 U Mains

Failure

Failure delay 0.5 to 990.0 s 5.0 s Parameters 7063 and 7064

relate to the nominal settings.

7062

7063

U Mains

Failure

U Mains

Failure

Mains OK delay 2 to 9900 s 60 s

U<

30 to 100 % of nominal

voltage

90 %

Parameter 7066 refers to the

mean value of the measured

voltage.

7064

U Mains

Failure

U>

100 to 130 % of

nominal voltage

110 %

7065

U Mains

Failure

Mains failure control

Start engine + open

MB

Start engine

Start engine +

open MB

7066

U Mains

Failure

U unbalance 2 to 100 % 100 %

7070 f Mains Failure

No. Setting Range Factory

setting

Description

7071 f Mains

Failure

Failure delay 0.5 to 990.0 s 5.0 s Parameters 7073 and 7074

relate to the nominal settings.

7072

f Mains

Failure

Mains OK delay 2 to 9900 s 60 s

7073

f Mains

Failure

f<

80.0 to 100.0 % of

nominal frequency

95.0 %

7074

f Mains

Failure

f>

100.0 to 120.0 % of

nominal frequency

105.0 %

PARAMETER LIST 4189340688R EN Page 159 of 222