7020 Start generator

No. Setting Range Factory

setting

Description

7021 Start

generator

Set point 5 to 100 % 80 % Peak shaving/mains power

export modes.

7022

7023

Start

generator

Start

generator

Timer 0.0 to 990.0 s 10.0 s

Minimum load 0 to 100 % 5 %

The set point refers to

parameter 7000 Mains power

setting.

7030 Stop generator

No. Setting Range Factory

setting

Description

7031 Stop

generator

Set point 0 to 80 % 60 % Peak shaving/mains power

export modes.

7032

Stop

generator

Timer 0.0 to 990.0 s 30.0 s

The set point refers to

parameter 7000 Mains power

setting.

3.4.2 Test

7040 Test (Mains controller)

No. Setting Range Factory

setting

Description

7041 Test Set point 1 to 20 000 kW 500 kW Simple test: Engine run only.

7042 Test Test time 0 to 999 min 5 min

Load test: Parallel to mains.

Full test: Disconnects mains.

7043 Test Return mode

Semi-auto mode

Auto mode

No mode change

Auto mode

7044 Test Test type

Simple test

Load test

Full test

Simple test

3.4.3 Controller settings

7050 Fixed power settings (Genset controller)

No. Setting Range Factory

setting

Description

7051 Fixed power

settings

7052

7053

7054

Fixed power

settings

Fixed power

settings

Q control

settings

Power

Cos phi

0 to 100 %

0.10 to 1.00 s

100 %

0.90

Fixed power parallel with mains

settings. Visibility of these

parameters depends on the

genset mode selected in

parameter 6070.

Cos phi

Inductive

Capacitive

Fixed Q set point -100 to 100 % 0 %

Inductive

For information on how

parameter 7055 works, see

Option A10.

7055

Q control

settings

Type

OFF

Superior

Fixed Q

OFF

PARAMETER LIST 4189340688R EN Page 158 of 222