3.4 Mains setup

3.4.1 Mains setup

6070 Plant mode (Mains controller only)

No. Setting Range Factory

setting

6071 Plant mode Auto Mains Failure

Peak shaving

Fixed power

Mains power export

Load take over

Description

This parameter can also be set

from the utility software,

Application supervision, Plant

settings.

7000 Mains power

No. Setting Range Factory

setting

Description

7001 Mains power Day -20000 to 20000 kW 750 kW Peak shaving/mains power

7002 Mains power Night -20000 to 20000 kW 1000 kW

export modes, set values in the

AGC-4 Mains controller.

7003 Mains power Scale

1 kW : 1 kW

1 kW : 10 kW

1 kW : 100 kW

1 kW : 1000 kW

1 kW : 1 kW

Parameter 7001/7002 must be

a positive value for mains

power export or peak shaving

mode.

Parameter 7001/7002 must be

a negative value for mains

power import.

Use menu 7260 to set up the

transducer.

7003 Mains power scaling

If you need a mains power set point of 100 MW, this does not fit in the range available in 7001. Configure the set point in

7001 as 10000 kW (10 MW), and use 1 kW : 10 kW in 7003.

7010 Daytime period

No. Setting Range Factory

setting

Description

7011 Daytime

period

Start hour 0 to 23 h 8 h Peak shaving/mains power

export modes.

7012

7013

Daytime

period

Daytime

period

Start minute 0 to 59 min 0 min

Stop hour 0 to 23 h 16 h

The period outside the daytime

period is defined as the night

period.

7014

Daytime

period

Stop minute 0 to 59 min 0 min

PARAMETER LIST 4189340688R EN Page 157 of 222