No. Setting Range Factory

setting

Description

7822 Excitation current protection

OFF

ON

OFF

Enables the excitation current

protection.

7823 Over-voltage protection

OFF

ON

OFF

Enables the over-voltage

protection.

7824 Diode fault

OFF

ON

OFF

Enables the diode fault

protection.

7825 Shutdown diodes

OFF

ON

OFF

Enables the shutdown diodes

function.

7831 DAVR communication error timer 0.0 to 100.0 s 0.0 s

A timer for an alarm for

communication error to the digital

AVR.

7832

DAVR communication error

output A

Not used

Relay 63

Not used

If the DAVR communication fails,

it is possible to activate a relay.

7833

DAVR communication error

output B

Not used

Relay 63

Not used

If the DAVR communication fails,

it is possible to activate a relay.

7834

DAVR communication error alarm

enable

OFF

ON

OFF

Enables/disables the alarm for

communication error between the

digital AVR and AGC-4.

7835

DAVR communication error alarm

fail class

Warning

Trip GB

Warning

Decides what AGC-4 should do,

if the DAVR communication alarm

occurs.

PARAMETER LIST 4189340688R EN Page 153 of 222