No. Setting Range Factory

setting

Description

Excitation sequence. This is

during the remanence phase.

7793

Magentization: Transformer

excitation current limit

0.0 to 300.0 % 100.0 %

Current maximum during

transformer excitation sequence.

The value is percentage of

nominal current.

7794

Induction motor starting current

limit

0.0 to 300.0 % 100.0 %

Current maximum during an

induction motor starting

sequence. The value is

percentage of nominal current.

7795 I stator limitation function enable

OFF

Magnetization

Inductive motor

OFF

Makes it possible to have the

stator current limitation functions

disabled, only induction motor

starting, or both induction motor

starting and transformer

excitation.

7801 PID factor 1 to 200 20

Makes it possible to make the

AVR regulation faster or slower.

7803 Write all settings

OFF

ON

OFF

When set to ON, AGC-4 will send

all the relevant parameters to the

digital AVR.

7804 DAVR bias range 1.0 to 30.0 % 10.0 %

This setting control defines the

outer limits for the regulation. 10

% on a 400 V generator means

that voltage can be regulated

from 360 to 440 V.

Decides who has the control.

7805 DAVR controls

OFF

ON

ON

• When set to ON, the digital

AVR is controlled by AGC-4.

• When set to OFF, the digital

AVR can be controlled by

EasyReg, and the digital AVR

will not receive any

parameters from AGC-4.

7806 DAVR bias analogue range

4 to 20 mA

Pot

0 to 10 V

0 to 10 V

If the digital AVR uses analogue

bias for regulation, this defines

the type of analogue interfacing

for the digital AVR. The analogue

input on the digital AVR is hard

coded to be at terminal AI1.

7811 PT100_1 threshold 50 to 200 °C 160 °C

7812 PT100_2 threshold 50 to 200 °C 160 °C

7813 PT100_3 threshold 50 to 200 °C 160 °C

Determines the maximum

temperature of the winding in

phase 1 of the alternator.

Determines the maximum

temperature of the winding in

phase 2 of the alternator.

Determines the maximum

temperature of the winding in

phase 3 of the alternator.

7821 Voltage loss detection enable

OFF

ON

OFF

Enables the voltage loss

protection.

PARAMETER LIST 4189340688R EN Page 152 of 222