No. Setting Range Factory

setting

Description

reading is not available, the unit

will display N.A.

When this setting has been set to

ON, the setting will be set to OFF

afterwards. This is only a pulse

that has been sent, but the

AGC-4 will still display the

readings, if any readings are

available.

7565 Digital AVR

OFF

Caterpillar CDVR

Leroy Somer D510C

DEIF DVC 310

DEIF DVC 550

NIDEC D550

OFF

Selects the CAN bus protocol for

interfacing between a digital AVR

and AGC-4.

Parameter 7565 "Caterpillar

CDVR" will not work if MTU

protocols are selected in

parameter 7561.

7741 DAVR primary voltage 400 to 32000 V 400 V

7742 DAVR secondary voltage 50 to 600 V 400 V

7743 DAVR busbar primary voltage 400 to 32000 V 400 V

7744 DAVR busbar secondary voltage 50 to 600 V 400 V

Decides the primary side of a

voltage transformer for the DVC.

(This is the transformer side that

is in contact with the generator

voltage).

Decides the secondary side of a

voltage transformer for the DVC.

(This is the transformer side that

is in contact with the digital

AVR).

Decides the primary side of a

voltage transformer to the

busbar. (This is the transformer

side that is in contact with the

busbar).

Decides the secondary side of a

voltage transformer to the

busbar. (This is the transformer

side that is in contact with the

digital AVR).

7745 DAVR VT enable

OFF

ON

OFF

When set to ON, the digital AVR

expects voltage measurements

on the busbar.

7746 DAVR AC config

0: Use AGC-4 AC

setting

1: 2-phase (W-U)

2: 2-phase (V-W)

3: 3-phase (U-V-W)

0

Phase selection for the DAVR.

See the DVC 550 Designer's

handbook for more information.

7751 PWM threshold 0.00 to 100.00 % 10.00 %

7752 Activation threshold 0.00 to 100.00 % 35.00 %

Decides the output of the start-on

threshold function. A higher

number will give a steeper slope

on the start-on threshold

function.

Decides the upper limit of the

start-on threshold function. When

this limit has been reached, the

PARAMETER LIST 4189340688R EN Page 150 of 222