No. Setting Range Factory
setting
Description
reading is not available, the unit
will display N.A.
When this setting has been set to
ON, the setting will be set to OFF
afterwards. This is only a pulse
that has been sent, but the
AGC-4 will still display the
readings, if any readings are
available.
7565 Digital AVR
OFF
Caterpillar CDVR
Leroy Somer D510C
DEIF DVC 310
DEIF DVC 550
NIDEC D550
OFF
Selects the CAN bus protocol for
interfacing between a digital AVR
and AGC-4.
Parameter 7565 "Caterpillar
CDVR" will not work if MTU
protocols are selected in
parameter 7561.
7741 DAVR primary voltage 400 to 32000 V 400 V
7742 DAVR secondary voltage 50 to 600 V 400 V
7743 DAVR busbar primary voltage 400 to 32000 V 400 V
7744 DAVR busbar secondary voltage 50 to 600 V 400 V
Decides the primary side of a
voltage transformer for the DVC.
(This is the transformer side that
is in contact with the generator
voltage).
Decides the secondary side of a
voltage transformer for the DVC.
(This is the transformer side that
is in contact with the digital
AVR).
Decides the primary side of a
voltage transformer to the
busbar. (This is the transformer
side that is in contact with the
busbar).
Decides the secondary side of a
voltage transformer to the
busbar. (This is the transformer
side that is in contact with the
digital AVR).
7745 DAVR VT enable
OFF
ON
OFF
When set to ON, the digital AVR
expects voltage measurements
on the busbar.
7746 DAVR AC config
0: Use AGC-4 AC
setting
1: 2-phase (W-U)
2: 2-phase (V-W)
3: 3-phase (U-V-W)
0
Phase selection for the DAVR.
See the DVC 550 Designer's
handbook for more information.
7751 PWM threshold 0.00 to 100.00 % 10.00 %
7752 Activation threshold 0.00 to 100.00 % 35.00 %
Decides the output of the start-on
threshold function. A higher
number will give a steeper slope
on the start-on threshold
function.
Decides the upper limit of the
start-on threshold function. When
this limit has been reached, the
PARAMETER LIST 4189340688R EN Page 150 of 222