1160 G/M/BA over-voltage 2

No. Setting Range Factory

setting

Description

1161 G/M/BA U> 2 Set point 100.0 to 120.0 % 105.0 % The alarm and fail class are

1162 G/M/BA U> 2 Timer 0.1 to 100.0 s 5.0 s

activated when the voltage has

been continuously above the

1163 G/M/BA U> 2 Relay output A Not used (option

dependent)

Not used programmed value during the

programmed delay.

1164 G/M/BA U> 2 Relay output B Not used (option

dependent)

1165 G/M/BA U> 2 Enable OFF

ON

Not used

OFF

1166 G/M/BA U> 2 Fail class F1 to F9 F2 (Warning)

1170 G/M/BA under-voltage 1

No. Setting Range Factory

setting

Description

1171 G/M/BA U< 1 Set point 40.0 to 100.0 % 97.0 % The alarm and fail class are

1172 G/M/BA U< 1 Timer 0.1 to 100.0 s 10.0 s

activated when the voltage has

been continuously under the

1173 G/M/BA U< 1 Relay output A Not used (option

dependent)

Not used programmed value during the

programmed delay.

1174 G/M/BA U< 1 Relay output B Not used (option

dependent)

1175 G/M/BA U< 1 Enable OFF

ON

Not used

OFF

1176 G/M/BA U< 1 Fail class F1 to F9 F2 (Warning)

1180 G/M/BA under-voltage 2

No. Setting Range Factory

setting

Description

1181 G/M/BA U< 2 Set point 40.0 to 100.0 % 95.0 % The alarm and fail class are

1182 G/M/BA U< 2 Timer 0.1 to 100.0 s 5.0 s

activated when the voltage has

been continuously under the

1183 G/M/BA U< 2 Relay output A Not used (option

dependent)

Not used programmed value during the

programmed delay.

1184 G/M/BA U< 2 Relay output B Not used (option

dependent)

1185 G/M/BA U< 2 Enable OFF

ON

Not used

OFF

1186 G/M/BA U< 2 Fail class F1 to F9 F2 (Warning)