3.2.11 Fuel transfer pump logic

6550 Fuel pump logic

No. Setting Range Factory

setting

Description

6551 Fuel pump

logic

6552

Fuel pump

logic

Set point start 0 to 100 % 20 % Note: When using RMI for fuel

pump logic, choose Auto

detection.

Set point stop 0 to 100 % 80 %

6553

Fuel pump

logic

Fill check time 0.1 to 300.0 s 60.0 s

6554

Fuel pump

logic

Relay output A

Not used (option

dependent)

Not used

6555

Fuel pump

logic

Set point

Multi-input 102

Multi-input 105

Multi-input 108

Ext. ana. In 1-8

CIO*

Auto detection

Multi-input

102

6556

Fuel pump

logic

Fail class F1 to F9 F2 (Warning)

*Note: There is a range of values for this.

3.2.12 Tank capacity

6910 Tank capacity

No. Setting Range Factory

setting

Description

6911 Tank capacity 0 to 9999 L 1250 L Set the capacity of the day

tank. The controller uses this

value and the fuel level to

calculate the fuel volume. The

fuel volume is shown in the

utility software in Application

supervision, Genset data,

General.

3.2.13 Digital AVR parameters

For DVC 550, the parameters are included in the DVC 550 Designer's handbook.

The digital AVR is affected by nominal parameters 6004, 6014, 6024, 6034, 6041, 6042, 6051, 6052, 6061 and 6062. For more

information, see Nominal settings.

No. Setting Range Factory

setting

Description

2262 Soft-start timer for CBE 0.0 to 999.0 s 5.0 s This setting determines the slope

of the soft-start during a CBE

start.

7564 EIC Auto view

OFF

ON

OFF

Enables AGC-4 to display

readings from the digital AVR. If a

PARAMETER LIST 4189340688R EN Page 149 of 222