3.2.11 Fuel transfer pump logic
6550 Fuel pump logic
No. Setting Range Factory
setting
Description
6551 Fuel pump
logic
6552
Fuel pump
logic
Set point start 0 to 100 % 20 % Note: When using RMI for fuel
pump logic, choose Auto
detection.
Set point stop 0 to 100 % 80 %
6553
Fuel pump
logic
Fill check time 0.1 to 300.0 s 60.0 s
6554
Fuel pump
logic
Relay output A
Not used (option
dependent)
Not used
6555
Fuel pump
logic
Set point
Multi-input 102
Multi-input 105
Multi-input 108
Ext. ana. In 1-8
CIO*
Auto detection
Multi-input
102
6556
Fuel pump
logic
Fail class F1 to F9 F2 (Warning)
*Note: There is a range of values for this.
3.2.12 Tank capacity
6910 Tank capacity
No. Setting Range Factory
setting
Description
6911 Tank capacity 0 to 9999 L 1250 L Set the capacity of the day
tank. The controller uses this
value and the fuel level to
calculate the fuel volume. The
fuel volume is shown in the
utility software in Application
supervision, Genset data,
General.
3.2.13 Digital AVR parameters
For DVC 550, the parameters are included in the DVC 550 Designer's handbook.
The digital AVR is affected by nominal parameters 6004, 6014, 6024, 6034, 6041, 6042, 6051, 6052, 6061 and 6062. For more
information, see Nominal settings.
No. Setting Range Factory
setting
Description
2262 Soft-start timer for CBE 0.0 to 999.0 s 5.0 s This setting determines the slope
of the soft-start during a CBE
start.
7564 EIC Auto view
OFF
ON
OFF
Enables AGC-4 to display
readings from the digital AVR. If a
PARAMETER LIST 4189340688R EN Page 149 of 222