04.01.2023 Views

agc-4-parameter-list-4189340688-uk

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

6610 Fan C failure

No. Setting Range Factory

setting

Description

6611 Fan C failure Timer 0.1 to 300.0 s 10.0 s

6612 Fan C failure Output A

6613 Fan C failure Output B

6614 Fan C failure Enable

Not used (option

dependent)

Not used (option

dependent)

OFF

ON

Not used

Not used

OFF

6615 Fan C failure Fail class F1 to F9 F2 (Warning)

6620 Fan D failure

No. Setting Range Factory

setting

Description

6621 Fan D failure Timer 0.1 to 300.0 s 10.0 s

6622 Fan D failure Output A

6623 Fan D failure Output B

6624 Fan D failure Enable

Not used (option

dependent)

Not used (option

dependent)

OFF

ON

Not used

Not used

OFF

6625 Fan D failure Fail class F1 to F9 F2 (Warning)

3.2.10 Engine heater

6320 Engine heater

No. Setting Range Factory

setting

Description

6321 Engine heater Set point 20 to 250 ° 40 ° Heater function for standstill.

6322 Engine heater Relay output A

6323 Engine heater Type

Not used (option

dependent)

Multi-input 102

Multi-input 105

Multi-input 108

EIC*

CIO*

Not used

Multi-input

102

6324 Engine heater Hysteresis 1 to 70 ° 3 °

6325 Engine heater Enable

OFF

ON

OFF

*Note: There is a range of values for each of these.

PARAMETER LIST 4189340688R EN Page 148 of 222