6580 Fan outputs

No. Setting Range Factory

setting

Description

6581 Fan A output Relay output A Not used (option

dependent)

Not used

Selection of relays for

activating fans.

6582 Fan B output Relay output B

6583 Fan C output Relay output C

6584 Fan D output Relay output D

Not used (option

dependent)

Not used (option

dependent)

Not used (option

dependent)

Not used

Not used

Not used

6585

Fan run. hour

reset

Reset

OFF

ON

OFF

6586

Fan start

delay

Timer 0.0 to 30.0 s 10.0 s

6590 Fan A failure

No. Setting Range Factory

setting

Description

6591 Fan A failure Timer 0.1 to 300.0 s 10.0 s

6592 Fan A failure Output A

6593 Fan A failure Output B

6594 Fan A failure Enable

Not used (option

dependent)

Not used (option

dependent)

OFF

ON

Not used

Not used

OFF

6595 Fan A failure Fail class F1 to F9 F2 (Warning)

6600 Fan B failure

No. Setting Range Factory

setting

Description

6601 Fan B failure Timer 0.1 to 300.0 s 10.0 s

6602 Fan B failure Output A

6603 Fan B failure Output B

6604 Fan B failure Enable

Not used (option

dependent)

Not used (option

dependent)

OFF

ON

Not used

Not used

OFF

6605 Fan B failure Fail class F1 to F9 F2 (Warning)