3.2.8 Cooling ventilation

6460 Max. ventilation

No. Setting Range Factory

setting

Description

6461 Max.

ventilation

Set point 20 to 250 ° 90 ° Ventilation fan control.

6462

Max.

ventilation

Relay output A

Not used (option

dependent)

Not used

6463

Max.

ventilation

Hysteresis 1 to 70 ° 5 °

6464

Max.

ventilation

Enable

OFF

ON

OFF

3.2.9 Fan logic

6560 Fan input settings

No. Setting Range Factory

setting

6561 Fan input Type See description Multi-input

102

6562

Fan prio

update

Priority 0 to 200 h 0 h

6563 1st prio fan Set point start 20 to 250 ° 70 °

6564 1st pr. fan Hysteresis 0 to 50 ° 10 °

6565 2nd prio fan Set point start 20 to 250 ° 80 °

6566 2nd pr. fan Hysteresis 0 to 50 ° 10 °

Description

Selection of fan input:

• Multi-input 102

• Multi-input 105

• Multi-input 108

• EIC

◦ Water/oil temp.

◦ Water temp.

◦ Oil temp.

◦ Ambient temp.

◦ Inter cool temp.

◦ Fuel temp.

• Ext. analog input: 1 to 8

(requires option H8)

• CIO (There is a range of

values for this.)

6570 3rd prio fan

No. Setting Range Factory

setting

Description

6571 3rd prio fan Set point start 20 to 250 ° 90 °

6572 3rd prio fan Hysteresis 0 to 50 ° 10 °

6573 4th prio fan Set point start 20 to 250 ° 100 °

6574 4th prio fan Hysteresis 0 to 50 ° 10 °

PARAMETER LIST 4189340688R EN Page 146 of 222