6250 Power derate 2

No. Setting Range Factory

setting

Description

6251 Power derate

2

6252

6253

6254

6255

6256

Power derate

2

Power derate

2

Power derate

2

Power derate

2

Power derate

2

Input

Multi-input, M-Logic,

EIC or CIO

Multi-input

102

Start derate 0 to 20000 units 16 units

Derate slope 0.1 to 100.0 %/unit 5.0 %/unit

Proportional

Enable

OFF

ON

OFF

ON

OFF

OFF

Limit 0.0 to 100.0 % 80.0 %

The derate function lowers the

max. power of the generator

set based on the input.

Input:

• Multi-input 102/105/108

• M-logic

• EIC Cooling water temp.

(SPN 110)

• EIC Oil temp. (SPN 175)

• EIC Ambient temp. (SPN

171)

• EIC Intercool temp. (SPN

52)

• EIC Fuel temp. (SPN 174)

• EIC Derate request (SPN

3644)

• CIO 308

1.08/1.11/1.14/1.17/1.20/1.

23/1.26/1.29

6260 Power derate 3

No. Setting Range Factory

setting

Description

6261 Power derate

3

6262

6263

6264

6265

6266

Power derate

3

Power derate

3

Power derate

3

Power derate

3

Power derate

3

Input

Multi-input, M-Logic,

EIC or CIO

Multi-input

102

Start derate 0 to 20000 units 16 units

Derate slope 0.1 to 100.0 %/unit 5.0 %/unit

Proportional

Enable

OFF

ON

OFF

ON

OFF

OFF

Limit 0.0 to 100.0 % 80.0 %

The derate function lowers the

max. power of the generator

set based on the input.

Input:

• Multi-input 102/105/108

• M-logic

• EIC Cooling water temp.

(SPN 110)

• EIC Oil temp. (SPN 175)

• EIC Ambient temp. (SPN

171)

• EIC Intercool temp. (SPN

52)

• EIC Fuel temp. (SPN 174)

• EIC Derate request (SPN

3644)

• CIO 308

1.08/1.11/1.14/1.17/1.20/1.

23/1.26/1.29