3.2.4 Running, start and stop

6160 Run status

No. Setting Range Factory

setting

Description

6161 Run status Timer 0.0 to 300.0 s 5.0 s If a relay output is used, the

relay must be set to Limit.

Not used (option

6162 Run status Relay output A

Not used

dependent)

6163 Run status Relay output B

6164 Run status Enable

Not used (option

dependent)

OFF

ON

Not used

OFF

6170 Running detection

No. Setting Range Factory

setting

Description

6171 Running

detect.

No. of teeth 0 to 500 teeth 0 teeth If parameter 6171 is set to 0,

the magnetic pickup input is

not active.

6172

Running

detect.

Type

Binary input

MPU input

Frequency

EIC rpm

Multi input 102

Multi input 105

Multi input 108

Frequency

6173

Running

detect.

Running RPM 0 to 4000 RPM 1000 RPM

6174

Running

detect.

Remove starter 1 to 2000 RPM 400 RPM

6175

Running

detect.

Pressure level 0.0 to 150.0 bar 0.0 bar

If parameter 6175 is set to 0.0,

the oil pressure running

detection is OFF.

6180 Starter

No. Setting Range Factory

setting

Description

6181 Starter Start prepare 0.0 to 600.0 s 5.0 s

6182 Starter Ext. prepare 0.0 to 600.0 s 0.0 s

6183 Starter Start ON time 1.0 to 180.0 s 5.0 s

6184 Starter Start OFF time 1.0 to 99.0 s 5.0 s

6185 Starter Input type

6186

Start

threshold

Multi-input 102

Multi-input 105

Multi-input 108

0.0 to 300.0 0.0

Multi-input

102

The parameters 6185 and

6186 relate to using multiinputs

as running feedback.

The units for parameter 6186

depend on the measurement

(for example, temperature or

pressure) chosen in 6185.

PARAMETER LIST 4189340688R EN Page 142 of 222