3.2.4 Running, start and stop
6160 Run status
No. Setting Range Factory
setting
Description
6161 Run status Timer 0.0 to 300.0 s 5.0 s If a relay output is used, the
relay must be set to Limit.
Not used (option
6162 Run status Relay output A
Not used
dependent)
6163 Run status Relay output B
6164 Run status Enable
Not used (option
dependent)
OFF
ON
Not used
OFF
6170 Running detection
No. Setting Range Factory
setting
Description
6171 Running
detect.
No. of teeth 0 to 500 teeth 0 teeth If parameter 6171 is set to 0,
the magnetic pickup input is
not active.
6172
Running
detect.
Type
Binary input
MPU input
Frequency
EIC rpm
Multi input 102
Multi input 105
Multi input 108
Frequency
6173
Running
detect.
Running RPM 0 to 4000 RPM 1000 RPM
6174
Running
detect.
Remove starter 1 to 2000 RPM 400 RPM
6175
Running
detect.
Pressure level 0.0 to 150.0 bar 0.0 bar
If parameter 6175 is set to 0.0,
the oil pressure running
detection is OFF.
6180 Starter
No. Setting Range Factory
setting
Description
6181 Starter Start prepare 0.0 to 600.0 s 5.0 s
6182 Starter Ext. prepare 0.0 to 600.0 s 0.0 s
6183 Starter Start ON time 1.0 to 180.0 s 5.0 s
6184 Starter Start OFF time 1.0 to 99.0 s 5.0 s
6185 Starter Input type
6186
Start
threshold
Multi-input 102
Multi-input 105
Multi-input 108
0.0 to 300.0 0.0
Multi-input
102
The parameters 6185 and
6186 relate to using multiinputs
as running feedback.
The units for parameter 6186
depend on the measurement
(for example, temperature or
pressure) chosen in 6185.
PARAMETER LIST 4189340688R EN Page 142 of 222