3.2 Genset setup

3.2.1 Genset mode

6070 Genset mode (Genset controller only)

No. Setting Range Factory

setting

6071 Genset mode Island

Auto Mains Failure

Peak shaving

Fixed power

Mains power export

Load take over

Power management (requires option G5)

Remote maintenance

Dry alternator (requires option T2)

Ventilation (requires option T2)

Description

This parameter can also be set

from the utility software,

Application supervision, Plant

settings.

3.2.2 Test

7040 Test (Genset controller)

No. Setting Range Factory

setting

Description

7041 Test Set point 1 to 100 % 80 % Simple test: Engine run only.

7042 Test Test time 0 to 999 min 5 min

Load test: Parallel to mains.

Full test: Disconnects mains.

7043 Test Return mode

Semi-auto mode

Auto mode

No mode change

Manual

Auto mode

7044 Test Test type

Simple test

Load test

Full test

Simple test

3.2.3 Run coil setup

6150 Run coil setup

No. Setting Range Factory

setting

Description

6151 Run coil setup ON time 0.0 to 600.0 s 1.0 s

6152 Run coil setup Type

Pulse

Continuous

Pulse

Pulse: Reset for each start

attempt.

Continuous: High throughout

all start attempts.

PARAMETER LIST 4189340688R EN Page 141 of 222