04.01.2023 Views

agc-4-parameter-list-4189340688-uk

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

3.1.11 Alarm horn

6130 Alarm horn

No. Setting Range Factory

setting

Description

6131 Alarm horn ON time 0.0 to 990.0 s 20.0 s If the setting is adjusted to 0 s,

the horn relay will be activated

continuously until the alarm is

acknowledged.

3.1.12 Alarm jump

6900 Alarm jump

No. Setting Range Factory

setting

Description

6901 Alarm jump Enable OFF

ON

ON

If an alarm appears:

• ON: Jump to alarm list view

on the display

• OFF: stay at present

display view.

3.1.13 Diagnostics

6700 Diagnostics

No. Setting Range Factory

setting

Description

6701 Diagnostics Timer 0 to 30 s 30 s Activates diagnostics mode to

read ECU data without starting

OFF

6702 Diagnostics Enable

OFF

the engine.

ON

3.1.14 I thermal demand

6840 I thermal demand

No. Setting Range Factory

setting

Description

6841 I thermal

demand

Timer 0 to 20 min. 8 min. Setup of I thermal period.

6842

I thermal

demand

Enable

OFF

ON

OFF

Enabled is used for reset.

6843

I max.

demand

Enable

OFF

ON

OFF

Reset I max. demand.

PARAMETER LIST 4189340688R EN Page 140 of 222