1130 Fast over-current 1

No. Setting Range Factory

setting

Description

1131 I>> 1 Set point 150.0 to 350.0 % 150.0 % The alarm settings relate to the

1132 I>> 1 Timer 0.0 to 100.0 s 2.0 s

nominal current setting. The

alarm and fail class are

1133 I>> 1 Relay output A Not used (option Not used activated when the current has

dependent)

been continuously above the

1134 I>> 1 Relay output B

programmed value during the

Not used (option Not used

programmed delay.

dependent)

1135 I>> 1 Enable OFF

ON

OFF

1136 I>> 1 Fail class F1 to F9 F3 (Trip GB)

1140 Fast over-current 2

No. Setting Range Factory

setting

Description

1141 I>> 2 Set point 150.0 to 350.0 % 200.0 % The alarm and fail class are

1142 I>> 2 Timer 0.0 to 100.0 s 0.5 s

activated when the current has

been continuously above the

1143 I>> 2 Relay output A Not used (option

dependent)

Not used programmed value during the

programmed delay.

1144 I>> 2 Relay output B Not used (option

dependent)

1145 I>> 2 Enable OFF

ON

Not used

OFF

1146 I>> 2 Fail class F1 to F9 F3 (Trip GB)

2.2.3 Voltage protections

1150 G/M/BA over-voltage 1

No. Setting Range Factory

setting

Description

1151 G/M/BA U> 1 Set point 100.0 to 120.0 % 103.0 % The alarm and fail class are

1152 G/M/BA U> 1 Timer 0.1 to 100.0 s 10.0 s

activated when the voltage has

been continuously above the

1153 G/M/BA U> 1 Relay output A Not used (option

dependent)

Not used programmed value during the

programmed delay.

1154 G/M/BA U> 1 Relay output B Not used (option

dependent)

1155 G/M/BA U> 1 Enable OFF

ON

Not used

OFF

1156 G/M/BA U> 1 Fail class F1 to F9 F2 (Warning)

PARAMETER LIST 4189340688R EN Page 14 of 222