6300 Service timer 3

No. Setting Range Factory

setting

Description

6301 Service timer

3

6302

Service timer

3

Enable

OFF

ON

ON

Running hours 0 to 9000 hrs 500 hrs

The timer is reset by setting

parameter 6306 to ON. After

reset, the parameter

automatically changes to OFF.

6303

6304

Service timer

3

Service timer

3

Days 1 to 1000 days 365 days

Fail class F1 to F9 F2 (Warning)

6305

Service timer

3

Output A

Not used (option

dependent)

Not used

6306

Service timer

3

Reset

OFF

ON

OFF

6310 Service timer 4

No. Setting Range Factory

setting

Description

6311 Service timer

4

6312

Service timer

4

Enable

OFF

ON

ON

Running hours 0 to 9000 hrs 500 hrs

The timer is reset by setting

parameter 6316 to ON. After

reset, the parameter

automatically changes to OFF.

6313

6314

Service timer

4

Service timer

4

Days 1 to 1000 days 365 days

Fail class F1 to F9 F2 (Warning)

6315

Service timer

4

Output A

Not used (option

dependent)

Not used

6316

Service timer

4

Reset

OFF

ON

OFF