6050 Busbar settings 1
No. Setting Range Factory
setting
Description
6051 BB setting 1 U primary 10 to 250,000 V* 400 V* If no voltage transformer is
6052 BB setting 1 U secondary 100 to 690 V 400 V
present, the primary and
secondary side values are set
6053 BB setting 1 Nominal U 1 10 to 250,000 V* 400 V* to generator nominal value.
6054 BB setting 1 Bus nom. set
Param set 1
Param set 2
Param set 1
*BB primary and nominal
voltage range and default
depend on the scaling set in
parameter 9030.
6060 Busbar settings 2
No. Setting Range Factory
setting
Description
6061 BB setting 2 U primary 10 to 250,000 V* 400 V* If no voltage transformer is
6062 BB setting 2 U secondary 100 to 690 V 400 V
present, the primary and
secondary side values are set
to generator nominal value.
6063 BB setting 2 Nominal U 2 10 to 250,000 V* 400 V*
*BB primary and nominal
voltage range and default
depend on the scaling set in
parameter 9030.
3.1.2 Breaker control
6230 Gen/Mains/Tie/Bus tie breaker control
No. Setting Range Factory
setting
Description
6231 GB/MB/TB/
BTB control
Close delay 0.0 to 30.0 s 2.0 s
6232
GB/MB/TB/
BTB control
Load time 0.0 to 30.0 s 0.0 s
Parameter 6232 is for compact
breakers (need to charge
spring before closing).
3.1.3 Date and time
6090 Date and time
No. Setting Range Factory
setting
Description
6091 Date and time Year 2001 to 2100 2008 Used to set up the clock in the
6092 Date and time Month 1 to 12 1
unit. Only available from the
display.
6093 Date and time Date 1 to 31 1
6094 Date and time Week day 1 to 7 1
6095 Date and time Hour 0 to 23 3
6096 Date and time Minute 0 to 59 5
PARAMETER LIST 4189340688R EN Page 132 of 222