6050 Busbar settings 1

No. Setting Range Factory

setting

Description

6051 BB setting 1 U primary 10 to 250,000 V* 400 V* If no voltage transformer is

6052 BB setting 1 U secondary 100 to 690 V 400 V

present, the primary and

secondary side values are set

6053 BB setting 1 Nominal U 1 10 to 250,000 V* 400 V* to generator nominal value.

6054 BB setting 1 Bus nom. set

Param set 1

Param set 2

Param set 1

*BB primary and nominal

voltage range and default

depend on the scaling set in

parameter 9030.

6060 Busbar settings 2

No. Setting Range Factory

setting

Description

6061 BB setting 2 U primary 10 to 250,000 V* 400 V* If no voltage transformer is

6062 BB setting 2 U secondary 100 to 690 V 400 V

present, the primary and

secondary side values are set

to generator nominal value.

6063 BB setting 2 Nominal U 2 10 to 250,000 V* 400 V*

*BB primary and nominal

voltage range and default

depend on the scaling set in

parameter 9030.

3.1.2 Breaker control

6230 Gen/Mains/Tie/Bus tie breaker control

No. Setting Range Factory

setting

Description

6231 GB/MB/TB/

BTB control

Close delay 0.0 to 30.0 s 2.0 s

6232

GB/MB/TB/

BTB control

Load time 0.0 to 30.0 s 0.0 s

Parameter 6232 is for compact

breakers (need to charge

spring before closing).

3.1.3 Date and time

6090 Date and time

No. Setting Range Factory

setting

Description

6091 Date and time Year 2001 to 2100 2008 Used to set up the clock in the

6092 Date and time Month 1 to 12 1

unit. Only available from the

display.

6093 Date and time Date 1 to 31 1

6094 Date and time Week day 1 to 7 1

6095 Date and time Hour 0 to 23 3

6096 Date and time Minute 0 to 59 5

PARAMETER LIST 4189340688R EN Page 132 of 222