6020 Nominal settings 3
No. Setting Range Factory
setting
Description
6021 Nom. settings
3
6022
Nom. settings
3
Frequency 48.0 to 62.0 Hz 60.0 Hz *Voltage and power range and
default depend on the scaling
set in parameter 9030.
Power 1 to 900,000 kW* 230 kW*
6023
6024
6025
Nom. settings
3
Nom. settings
3
Nom. settings
3
Current 0 to 9000 A 345 A
Voltage 10 to 250,000 V* 480 V*
RPM 100 to 4000 RPM 1800 RPM
6030 Nominal settings 4
No. Setting Range Factory
setting
Description
6031 Nom. settings
4
6032
Nom. settings
4
Frequency 48.0 to 62.0 Hz 60.0 Hz *Voltage and power range and
default depend on the scaling
set in parameter 9030.
Power 1 to 900,000 kW* 230 kW*
6033
6034
6035
Nom. settings
4
Nom. settings
4
Nom. settings
4
Current 0 to 9000 A 345 A
Voltage 10 to 250,000 V* 480 V*
RPM 100 to 4000 RPM 1800 RPM
6040 Gen/Mains/busbar A transformer
No. Setting Range Factory
setting
Description
6041 G/M/BA
transformer
6042
G/M/BA
transformer
U primary
U secondary
10 to 250,000 V*
100 to 690 V
400 V*
400 V
If no voltage transformer is
present, the primary and
secondary side values are set
to generator nominal value.
6043
6044
G/M/BA
transformer
G/M/BA
transformer
I primary 5 to 9000 A 1000 A
I secondary 1 to 5 A 5 A
*Gen/mains/busbar primary
voltage range and default
depend on the scaling set in
parameter 9030.
PARAMETER LIST 4189340688R EN Page 131 of 222