04.01.2023 Views

agc-4-parameter-list-4189340688-uk

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

3. System parameters

3.1 General setup

3.1.1 Nominal settings

6000 Nominal settings 1

No. Setting Range Factory

setting

Description

6001 Nom. settings

1

6002

Nom. settings

1

Frequency

Power

48.0 to 62.0 Hz

1 to 900,000 kW*

50.0 Hz

480 kW*

The nominal settings to be

used is set in parameter 6006.

A binary input or selection in

M-logic can also be used.

6003

6004

Nom. settings

1

Nom. settings

1

Current 0 to 9000 A 867 A

Voltage 10 to 250,000 V* 400 V*

*Voltage and power range and

default depend on the scaling

set in parameter 9030.

6005

Nom. settings

1

RPM 100 to 4000 RPM 1500 RPM

6006

Nom. settings

1

Setting 1 to 4 1

6010 Nominal settings 2

No. Setting Range Factory

setting

Description

6011 Nom. settings

2

6012

Nom. settings

2

Frequency 48.0 to 62.0 Hz 50.0 Hz *Voltage and power range and

default depend on the scaling

set in parameter 9030.

Power 1 to 900,000 kW* 230 kW*

6013

6014

6015

Nom. settings

2

Nom. settings

2

Nom. settings

2

Current 0 to 9000 A 345 A

Voltage 10 to 250,000 V* 480 V*

RPM 100 to 4000 RPM 1500 RPM

PARAMETER LIST 4189340688R EN Page 130 of 222