7940 CAN2 communication error

No. Setting Range Factory

setting

Description

7941

CAN2 com

error

7942 CAN2 com

error

7943 CAN2 com

error

Timer 10.0 to 600.0 s 10.0 s

Relay output A

Relay output B

Not used (option

dependent)

Not used (option

dependent)

Not used

Not used

Option:

• External I/O modules

(H8.2)

Note: If both options H8.x are

present, an error on any of

these will activate the alarm.

7944 CAN2 com

error

Enable

OFF

ON

ON

7945

CAN2 com

error

Fail class F1 to F9 F2 (Warning)

PARAMETER LIST 4189340688R EN Page 127 of 222