Create successful ePaper yourself
Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.
7700 EIC Cyl dif. 2 (with option H5, H7, H12, or option H6)
No. Setting Range Factory
setting
Description
7701 EIC Cyl dif. 2 Set point 0 to 9999 ° 110 °
7702 EIC Cyl dif. 2 Timer 0.0 to 100.0 s 5.0 s
7703 EIC Cyl dif. 2 Relay output A Not used (option
dependent)
7704 EIC Cyl dif. 2 Relay output B Not used (option
dependent)
7705 EIC Cyl dif. 2 Enable OFF
ON
Not used
Not used
OFF
7706 EIC Cyl dif. 2 Fail class F1 to F9 F2 (Warning)
2.9.3 Power management communication error
7870 Any BTB missing/appl. hazard
No. Setting Range Factory
setting
7871
Any BTB
missing
7872 Appl. hazard Enable OFF
ON
Fail class F1 to F9 F2 (Warning)
7873 Appl. hazard Fail class F1 to F9 F2 (Warning)
ON
Description
The “Any BTB missing” alarm
is activated if the
communication to any BTB unit
failed.
The application hazard alarm is
activated if different
applications are installed in the
controllers.
2.9.4 Internal CAN communication error
7930 CAN1 communication error
No. Setting Range Factory
setting
Description
7931
CAN1 com
error
7932 CAN1 com
error
7933 CAN1 com
error
Timer 10.0 to 600.0 s 10.0 s
Relay output A
Relay output B
Not used (option
dependent)
Not used (option
dependent)
Not used
Not used
Option:
• External I/O modules
(H8.2)
Note: If both options H8.x are
present, an error on any of
these will activate the alarm.
7934 CAN1 com
error
Enable
OFF
ON
ON
7935
CAN1 com
error
Fail class F1 to F9 F2 (Warning)
PARAMETER LIST 4189340688R EN Page 126 of 222