7700 EIC Cyl dif. 2 (with option H5, H7, H12, or option H6)

No. Setting Range Factory

setting

Description

7701 EIC Cyl dif. 2 Set point 0 to 9999 ° 110 °

7702 EIC Cyl dif. 2 Timer 0.0 to 100.0 s 5.0 s

7703 EIC Cyl dif. 2 Relay output A Not used (option

dependent)

7704 EIC Cyl dif. 2 Relay output B Not used (option

dependent)

7705 EIC Cyl dif. 2 Enable OFF

ON

Not used

Not used

OFF

7706 EIC Cyl dif. 2 Fail class F1 to F9 F2 (Warning)

2.9.3 Power management communication error

7870 Any BTB missing/appl. hazard

No. Setting Range Factory

setting

7871

Any BTB

missing

7872 Appl. hazard Enable OFF

ON

Fail class F1 to F9 F2 (Warning)

7873 Appl. hazard Fail class F1 to F9 F2 (Warning)

ON

Description

The “Any BTB missing” alarm

is activated if the

communication to any BTB unit

failed.

The application hazard alarm is

activated if different

applications are installed in the

controllers.

2.9.4 Internal CAN communication error

7930 CAN1 communication error

No. Setting Range Factory

setting

Description

7931

CAN1 com

error

7932 CAN1 com

error

7933 CAN1 com

error

Timer 10.0 to 600.0 s 10.0 s

Relay output A

Relay output B

Not used (option

dependent)

Not used (option

dependent)

Not used

Not used

Option:

• External I/O modules

(H8.2)

Note: If both options H8.x are

present, an error on any of

these will activate the alarm.

7934 CAN1 com

error

Enable

OFF

ON

ON

7935

CAN1 com

error

Fail class F1 to F9 F2 (Warning)