04.01.2023 Views

agc-4-parameter-list-4189340688-uk

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

7670 EIC coolant level 1 (with option H5, H7, H12, or option H6)

No. Setting Range Factory

setting

Description

7671

EIC coolant

level 1

Set point 0 to 100 % 20 %

7672 EIC coolant

level 1

Timer 0.0 to 100.0 s 5.0 s

7673 EIC coolant

level 1

Relay output A

Not used (option

dependent)

Not used

7674 EIC coolant

level 1

Relay output B

Not used (option

dependent)

Not used

7675 EIC coolant

level 1

Enable

OFF

ON

OFF

7676

EIC coolant

level 1

Fail class F1 to F9 F2 (Warning)

7680 EIC coolant level 2 (with option H5, H7, H12, or option H6)

No. Setting Range Factory

setting

Description

7681

EIC coolant

level 2

Set point 0 to 100 % 10 %

7682 EIC coolant

level 2

Timer 0.0 to 100.0 s 5.0 s

7683 EIC coolant

level 2

Relay output A

Not used (option

dependent)

Not used

7684 EIC coolant

level 2

Relay output B

Not used (option

dependent)

Not used

7685 EIC coolant

level 2

Enable

OFF

ON

OFF

7686

EIC coolant

level 2

Fail class

F1 to F9

F5

(Shutdown)

7690 EIC Cyl dif. 1 (with option H5, H7, H12, or option H6)

No. Setting Range Factory

setting

Description

7691 EIC Cyl dif. 1 Set point 0 to 9999 ° 100

7692 EIC Cyl dif. 1 Timer 0.0 to 100.0 s 5.0 s

7693 EIC Cyl dif. 1 Relay output A Not used (option

dependent)

7694 EIC Cyl dif. 1 Relay output B Not used (option

dependent)

7695 EIC Cyl dif. 1 Enable OFF

ON

Not used

Not used

OFF

7696 EIC Cyl dif. 1 Fail class F1 to F9 F2 (Warning)

PARAMETER LIST 4189340688R EN Page 125 of 222