7580 EIC warning (with option H5, H7, H12, or option H6)

No. Setting Range Factory

setting

Description

7581 EIC warning Timer 0.0 to 100.0 s 0.0 s

7582 EIC warning Relay output A Not used (option

dependent)

7583 EIC warning Relay output B Not used (option

dependent)

7584 EIC warning Enable OFF

ON

Not used

Not used

ON

7585 EIC warning Fail class F1 to F9 F2 (Warning)

7590 EIC shutdown (with option H5, H7, H12, or option H6)

No. Setting Range Factory

setting

Description

7591 EIC shutdown Timer 0.0 to 100.0 s 0.0 s

7592 EIC shutdown Relay output A Not used (option

dependent)

7593 EIC shutdown Relay output B Not used (option

dependent)

7594 EIC shutdown Enable OFF

ON

7595 EIC shutdown Fail class F1 to F9

Not used

Not used

OFF

F5

(Shutdown)

7600 EIC overspeed (with option H5, H7, H12, or option H6)

No. Setting Range Factory

setting

Description

7601

EIC overspeed

Set point 100.0 to 150.0 % 110.0 %

7602 EIC overspeed

Timer 0.0 to 100.0 s 5.0 s

7603 EIC overspeed

Relay output A

Not used (option

dependent)

Not used

7604 EIC overspeed

Relay output B

Not used (option

dependent)

Not used

7605 EIC overspeed

Enable

OFF

ON

OFF

7606

EIC overspeed

Fail class F1 to F9 F2 (Warning)

PARAMETER LIST 4189340688R EN Page 122 of 222