04.01.2023 Views

agc-4-parameter-list-4189340688-uk

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

1040 Over-current 2

No. Setting Range Factory

setting

Description

1041 I>2 Set point 50.0 to 200.0 % 120.0 % The alarm and fail class are

1042 I>2 Timer 0.1 to 3200.0 s 5.0 s

activated when the current has

been continuously above the

1043 I>2 Relay output A Not used (option

dependent)

Not used programmed value during the

programmed delay.

1044 I>2 Relay output B Not used (option

dependent)

1045 I>2 Enable OFF

ON

Not used

ON

1046 I>2 Fail class F1 to F9 F3 (Trip GB)

1050 Over-current 3

No. Setting Range Factory

setting

Description

1051 I>3 Set point 50.0 to 200.0 % 115.0 % The alarm and fail class are

1052 I>3 Timer 0.1 to 3200.0 s 10.0 s

activated when the current has

been continuously above the

1053 I>3 Relay output A Not used (option

dependent)

Not used programmed value during the

programmed delay.

1054 I>3 Relay output B Not used (option

dependent)

1055 I>3 Enable OFF

ON

Not used

ON

1056 I>3 Fail class F1 to F9 F3 (Trip GB)

1060 Over-current 4

No. Setting Range Factory

setting

Description

1061 I>4 Set point 50.0 to 200.0 % 120.0 % The alarm and fail class are

1062 I>4 Timer 0.1 to 3200.0 s 5.0 s

activated when the current has

been continuously above the

1063 I>4 Relay output A Not used (option

dependent)

Not used programmed value during the

programmed delay.

1064 I>4 Relay output B Not used (option

dependent)

1065 I>4 Enable OFF

ON

Not used

ON

1066 I>4 Fail class F1 to F9 F3 (Trip GB)

PARAMETER LIST 4189340688R EN Page 12 of 222