6510 Stop switchboard error

No. Setting Range Factory

setting

Description

6511 Stp. swbd

error

6512 Stp. swbd

error

Timer

Relay output A

0.0 to 999.0 s

Not used (option

1.0 s

Not used

If the binary input switchboard

error activates, the generator

will be stopped.

dependent)

6513 Stp. swbd

error

Relay output B

Not used (option

dependent)

Not used

6514

Stp. swbd

error

Enable

OFF

ON

OFF

6515

Stp. swbd

error

Fail class

F1 to F9

F5

(Shutdown)

2.8.7 Switchboard error: Not in auto

6540 Not in auto

No. Setting Range Factory

setting

Description

6541 Not in auto Timer 10.0 to 900.0 s 300.0 s

6542 Not in auto Relay output A Not used (option

dependent)

6543 Not in auto Relay output B Not used (option

dependent)

Not used

Not used

6544 Not in auto Enable

OFF

ON

OFF

6545 Not in auto Fail class F1 to F9 F2 (Warning)

2.8.8 Oil renewal

6890 Oil renewal

No. Setting Range Factory

setting

Description

6891 Oil renewal Set point 1 to 999 h 750 h Setup of oil renewal.

6892 Oil renewal Relay output A Not used (option

dependent)

Not used

6893 Adj. reset

value

Password level

Basic

Customer

Service

Basic

PARAMETER LIST 4189340688R EN Page 119 of 222