2.8.3 Running detection

6350 Running detection

No. Setting Range Factory

setting

Description

6351 Running

detection

6352 Ext. engine

Stop

Timer 1.0 s to 1200.0 s 10.0 s -

Timer 1.0 s to 1200.0 s 10.0 s

6353

Ext. engine

Stop

Enable

OFF

ON

ON

6354

Ext. engine

Stop

Fail class F1 to F9 F2 (Warning)

2.8.4 Battery tests

6410 Battery test

No. Setting Range Factory

setting

Description

6411 Battery test Set point 8.0 to 32.0 V 18.0 V If the battery voltage drops

6412 Battery test Timer 1.0 to 300.0 s 20.0 s

below set point during crank

test the alarm activates.

6413 Battery test Type Power supply Power supply If the type is configured with +

Multi-input 102

Multi-input105

Multi-input 108

Power supply 98/99

(+ Start Sequence)

Start Sequence, the timer is

disabled and the number of

start attempts configured in

Start attempts (parameter

6190) is run without activating

the run coil. After the

6414 Battery test Relay output A Not used (option Not used

sequence, the alarm Start

dependent)

failure (parameter 4570) is

6415 Battery test Enable

OFF

activated.

OFF

ON

6416 Battery test Fail class F1 to F9 F2 (Warning)

6420 Auto battery test

No. Setting Range Factory

setting

Description

6421 Auto battery

test

Enable

OFF

ON

OFF

Automatic battery test time

setting.

6422 Auto battery

test

6423 Auto battery

test

6424 Auto battery

test

Day Monday to Sunday Monday

Hours 0 to 23 h 10 h

Week 1 to 52 52

6425

Auto battery

test

Relay output A

Not used (option

dependent)

Not used

PARAMETER LIST 4189340688R EN Page 116 of 222