04.01.2023 Views

agc-4-parameter-list-4189340688-uk

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

4990 U> auxiliary power supply terminal 98

No. Setting Range Factory

setting

Description

4991 U> aux. term.

98

4992 U> aux. term.

98

4993 U> aux. term.

98

Set point

Timer

8.0 to 32.0 V DC

0.0 s to 999.0 s

30.0 V DC

1.0 s

The power supply on terminal

98 and 99 has continuously

been above the adjusted set

point during the programmed

delay time.

Relay output A Not used (option Not used

dependent)

4994 U> aux. term.

98

Relay output B

Not used (option

dependent)

Not used

4995

U> aux. term.

98

Enable

OFF

ON

ON

4996

U> aux. term.

98

Fail class F1 to F9 F2 (Warning)