- Page 1 and 2:
PARAMETER LISTAGC-4DEIF A/S · Fris
- Page 3 and 4:
2.6 Input/output parameters: Analog
- Page 5 and 6:
3.7.3 RMI 108......................
- Page 7 and 8:
1. General information1.1 Warnings,
- Page 9 and 10:
2. Alarm list2.1 General informatio
- Page 11 and 12:
2.2 Protection parameters2.2.1 Reve
- Page 13 and 14:
1080 G I> inverseNo. Setting Range
- Page 15 and 16:
1160 G/M/BA over-voltage 2No. Setti
- Page 17 and 18:
1210 G/M/BA over-frequency 1No. Set
- Page 19 and 20:
1270 Busbar over-voltage 1No. Setti
- Page 21 and 22:
1320 Busbar under-voltage 3No. Sett
- Page 23 and 24:
1380 Busbar under-frequency 1No. Se
- Page 25 and 26:
2.2.7 Mains failure protections1420
- Page 27 and 28:
2.2.8 Overload protections1450 Over
- Page 29 and 30:
1710 unbalanced current 2No. Settin
- Page 31 and 32:
1560 Negative sequence selection (w
- Page 33 and 34:
2.2.16 Busbar unbalance voltage1620
- Page 35 and 36:
1700 Time-dependent under-voltage 2
- Page 37 and 38:
1850 NEL 3 busbar under-frequencyNo
- Page 39 and 40:
1980 GB/MB external tripNo. Setting
- Page 41 and 42:
2150 Phase sequence error DG/Mains/
- Page 43 and 44:
2270 Close before excitation failur
- Page 45 and 46:
2.4 Control parameters: Regulation2
- Page 47 and 48:
2.5 Input/output parameters: Binary
- Page 49 and 50:
3140 Digital input 44 (requires opt
- Page 51 and 52:
3200 Digital input 50 (requires opt
- Page 53 and 54:
2.5.3 Digital input 91-97 setup (re
- Page 55 and 56:
3390 Digital input 97 (requires opt
- Page 57 and 58:
3450 Digital input 114No. Setting R
- Page 59 and 60:
3510 Digital input 128 (requires op
- Page 61 and 62: 2.5.8 M-Logic alarm 1-5 setup3570 M
- Page 63 and 64: 2.6 Input/output parameters: Analog
- Page 65 and 66: 4060 4-20 mA 95.1 (requires option
- Page 67 and 68: 2.6.2 Analogue input setup (require
- Page 69 and 70: 4860 4-20 mA 131.1 (requires option
- Page 71 and 72: 2.6.3 Analogue input setup (require
- Page 73 and 74: 4020 Wire fail 91 (requires option
- Page 75 and 76: 4040 Pt100 93.2 (requires option M1
- Page 77 and 78: 4070 V DC 95.2 (requires option M16
- Page 79 and 80: 4100 4-20 mA 97.2 (requires option
- Page 81 and 82: 4800 Pt100 127.1 (requires option M
- Page 83 and 84: 4830 V DC 129.1 (requires option M1
- Page 85 and 86: 4860 4-20 mA 131.1 (requires option
- Page 87 and 88: 4890 Wire fail 131 (requires option
- Page 89 and 90: 4900 Pt100 133.2 (requires option M
- Page 91 and 92: 4150 V DC 102.2No. Setting Range Fa
- Page 93 and 94: 4210 RMI water 102.2No. Setting Ran
- Page 95 and 96: 4270 V DC 105.1No. Setting Range Fa
- Page 97 and 98: 4330 RMI water 105.1No. Setting Ran
- Page 99 and 100: 4390 4-20 mA 108.2No. Setting Range
- Page 101 and 102: 4450 RMI oil 108.2No. Setting Range
- Page 103 and 104: 2.7.4 Speed and running feedback se
- Page 105 and 106: 4570 Start failureNo. Setting Range
- Page 107 and 108: 4610 Delta analogue 1.1No. Setting
- Page 109 and 110: 4680 Delta analogue 4.1No. Setting
- Page 111: 4750 Delta analogue 7.1No. Setting
- Page 115 and 116: 2.8 System parameters: General setu
- Page 117 and 118: 6430 Battery asymmetryNo. Setting R
- Page 119 and 120: 6510 Stop switchboard errorNo. Sett
- Page 121 and 122: 2.9 System parameters: Communicatio
- Page 123 and 124: 7610 EIC coolant temperature 1 (wit
- Page 125 and 126: 7670 EIC coolant level 1 (with opti
- Page 127 and 128: 7940 CAN2 communication errorNo. Se
- Page 129 and 130: 2.10.3 External analogue input scal
- Page 131 and 132: 6020 Nominal settings 3No. Setting
- Page 133 and 134: 3.1.4 Master clock6400 Master clock
- Page 135 and 136: 6300 Service timer 3No. Setting Ran
- Page 137 and 138: 6970 Command start/stop timer 2No.
- Page 139 and 140: 6990 Command start/stop timer 4No.
- Page 141 and 142: 3.2 Genset setup3.2.1 Genset mode60
- Page 143 and 144: 6190 Start attemptsNo. Setting Rang
- Page 145 and 146: 6250 Power derate 2No. Setting Rang
- Page 147 and 148: 6580 Fan outputsNo. Setting Range F
- Page 149 and 150: 3.2.11 Fuel transfer pump logic6550
- Page 151 and 152: No. Setting Range FactorysettingDes
- Page 153 and 154: No. Setting Range FactorysettingDes
- Page 155 and 156: 3.3.2 Cab Message 1 source address1
- Page 157 and 158: 3.4 Mains setup3.4.1 Mains setup607
- Page 159 and 160: 7050 Fixed power settings (Mains co
- Page 161 and 162: 3.4.7 Power offset7220 Power offset
- Page 163 and 164:
3.5 Power management setup3.5.1 Pow
- Page 165 and 166:
8290 Detection of BB measurement fa
- Page 167 and 168:
8250 Available power 4 (requires op
- Page 169 and 170:
8880 Load-dependent start/stop calc
- Page 171 and 172:
3.5.6 Power management internal com
- Page 173 and 174:
7950 KL320x config (requires option
- Page 175 and 176:
3.7.2 RMI 105NOTERMI 105 settings a
- Page 177 and 178:
3.7.4 Multi-input selections 102, 1
- Page 179 and 180:
3.7.7 4-20 mA input scaling11010 4
- Page 181 and 182:
13010 Oil pressure, coolant temp, f
- Page 183 and 184:
No. Setting Range FactorysettingDes
- Page 185 and 186:
No. Setting Range FactorysettingDes
- Page 187 and 188:
9070 M4 software versionNo.Descript
- Page 189 and 190:
9160 User-defined applicationNo. Se
- Page 191 and 192:
3.9.17 Data loggingThis menu is to
- Page 193 and 194:
4. Control parameters4.1 Synchronis
- Page 195 and 196:
2250 Close before excitationNo. Set
- Page 197 and 198:
2570 Frequency control relay output
- Page 199 and 200:
2650 Reactive power control analogu
- Page 201 and 202:
2760 OverlapNo. Setting Range Facto
- Page 203 and 204:
2810 AVR limitingNo. Setting Range
- Page 205 and 206:
No. Setting Range FactorysettingDes
- Page 207 and 208:
5140 Relay 63 (requires option M12)
- Page 209 and 210:
5240 Relay 128 (requires option M14
- Page 211 and 212:
4.4.2 Analogue output limits5720 PW
- Page 213 and 214:
5850 S output (requires option E2,
- Page 215 and 216:
5910 U BB output (requires option E
- Page 217 and 218:
5970 P total available (requires op
- Page 219 and 220:
5. Utility software settingsThe uti
- Page 221 and 222:
INFOThe governor and AVR regulation