2.2 Protection parameters

2.2.1 Reverse power protections

1000 Reverse power 1

No. Setting Range Factory

setting

Description

1001 -P>1 Set point -200.0 to 0.0 % -5.0 % The alarm and fail class are

1002 -P>1 Timer 0.1 to 100.0 s 5.0 s

activated when the reverse

power has been continuously

1003 -P>1 Relay output A Not used (option

dependent)

Not used above the programmed value

during the programmed delay.

1004 -P>1 Relay output B Not used (option

dependent)

1005 -P>1 Enable OFF

ON

Not used

ON

1006 -P>1 Fail class F1 to F9 F3 (Trip GB)

1010 Reverse power 2

No. Setting Range Factory

setting

Description

1011 -P>2 Set point -200.0 to 0.0 % -5.0 % The alarm and fail class are

1012 -P>2 Timer 0.1 to 100.0 s 10.0 s

activated when the reverse

power has been continuously

1013 -P>2 Relay output A Not used (option

dependent)

Not used above the programmed value

during the programmed delay.

1014 -P>2 Relay output B Not used (option

dependent)

1015 -P>2 Enable OFF

ON

Not used

ON

1016 -P>2 Fail class F1 to F9 F3 (Trip GB)

2.2.2 Over-current protections

1030 Over-current 1

No. Setting Range Factory

setting

Description

1031 I>1 Set point 50.0 to 200.0 % 115.0 % The alarm and fail class are

1032 I>1 Timer 0.1 to 3200.0 s 10.0 s

activated when the current has

been continuously above the

1033 I>1 Relay output A Not used (option

dependent)

Not used programmed value during the

programmed delay.

1034 I>1 Relay output B Not used (option

dependent)

1035 I>1 Enable OFF

ON

Not used

ON

1036 I>1 Fail class F1 to F9 F2 (Warning)

PARAMETER LIST 4189340688R EN Page 11 of 222