04.01.2023 Views

agc-4-parameter-list-4189340688-uk

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

4640 Delta analogue 2.2

No. Setting Range Factory

setting

Description

4641 Delta Ana2.2 Set point -9999 to 9999 10 Delta analogue alarm setting

4642 Delta Ana2.2 Timer 0.0 s to 999.0 s 5.0 s

2.2.

4643 Delta Ana2.2 Relay output A Not used (option

dependent)

4644 Delta Ana2.2 Relay output B Not used (option

dependent)

Not used

Not used

4645 Delta Ana2.2 Enable

OFF

ON

OFF

4646 Delta Ana2.2 Fail class F1 to F9 F2 (Warning)

4650 Delta analogue 3.1

No. Setting Range Factory

setting

Description

4651 Delta Ana3.1 Set point -9999 to 9999 10 Delta analogue alarm setting

4652 Delta Ana3.1 Timer 0.0 s to 999.0 s 5.0 s

3.1.

4653 Delta Ana3.1 Relay output A Not used (option

dependent)

4654 Delta Ana3.1 Relay output B Not used (option

dependent)

Not used

Not used

4655 Delta Ana3.1 Enable

OFF

ON

OFF

4656 Delta Ana3.1 Fail class F1 to F9 F2 (Warning)

4660 Delta analogue 3.2

No. Setting Range Factory

setting

Description

4661 Delta Ana3.2 Set point -9999 to 9999 10 Delta analogue alarm setting

4662 Delta Ana3.2 Timer 0.0 s to 999.0 s 5.0 s

3.2.

4663 Delta Ana3.2 Relay output A Not used (option

dependent)

4664 Delta Ana3.2 Relay output B Not used (option

dependent)

Not used

Not used

4665 Delta Ana3.2 Enable

OFF

ON

OFF

4666 Delta Ana3.2 Fail class F1 to F9 F2 (Warning)

PARAMETER LIST 4189340688R EN Page 108 of 222