4570 Start failure

No. Setting Range Factory

setting

Description

4571 Start failure Relay output A Not used (option

dependent)

4572 Start failure Relay output B Not used (option

dependent)

Not used

Not used

The start failure alarm occurs if

the genset has not started after

the number of start attempts.

4573 Start failure Fail class F1 to F9 F1 (Block)

4580 Stop failure

No. Setting Range Factory

setting

Description

4581 Stop failure Timer 10.0 to 120.0 s 30.0 s

4582 Stop failure Relay output A Not used (option

dependent)

4583 Stop failure Relay output B Not used (option

dependent)

4584 Stop failure Enable OFF

ON

4585 Stop failure Fail class F1 to F9

Not used

Not used

ON

F5

(Shutdown)

A stop failure alarm will appear

if the primary running feedback

or the generator voltage and

frequency are still present after

the delay time has expired.

4590 Underspeed 1

No. Setting Range Factory

setting

Description

4591 Underspeed 1 Set point 50 to 100 % 90 % The set point in percentage

4592 Underspeed 1 Timer 0.0 to 100.0 s 5.0 s

relates to nominal RPM.

4593 Underspeed 1 Relay output A Not used (option

dependent)

4594 Underspeed 1 Relay output B Not used (option

dependent)

4595 Underspeed 1 Enable OFF

ON

Not used

Not used

OFF

4596 Underspeed 1 Fail class F1 to F9 F2 (Warning)

PARAMETER LIST 4189340688R EN Page 105 of 222