4540 Running feedback failure

No. Setting Range Factory

setting

Description

4541

Running

feedback

failure

4542 Running

feedback

failure

4543 Running

feedback

failure

Timer 0.0 to 20.0 s 2.0 s

Relay output A

Relay output B

Not used (option

dependent)

Not used (option

dependent)

Not used

Not used

If running is detected on the

frequency (secondary), but the

primary running feedback (for

example, a digital input) has

not detected running, this

alarm will be raised after the

adjusted delay time.

4544 Running

feedback

failure

Enable

OFF

ON

ON

4545

Running

feedback

failure

Fail class F1 to F9 F2 (Warning)

4550 Magnetic pick-up wire break

No. Setting Range Factory

setting

Description

4551 MPU wire

break

4552 MPU wire

break

Relay output A

Relay output B

Not used (option

dependent)

Not used (option

dependent)

Not used

Not used

The wire break monitoring is

only active when the engine is

at stand still.

4553 MPU wire

break

Enable

OFF

ON

OFF

4554

MPU wire

break

Fail class F1 to F9 F2 (Warning)

4560 Hz/voltage failure

No. Setting Range Factory

setting

Description

4561 Hz/V failure Timer 1.0 to 99.0 s 30.0 s If the frequency and voltage

are not within the limits after

4562 Hz/V failure Relay output A Not used (option Not used

the running feedback is

dependent)

received, this alarm will be

4563 Hz/V failure Relay output B Not used (option Not used raised when the delay time has

4564 Hz/V failure Enable

dependent)

OFF

ON

ON

expired. Limits are placed in

menu 2110 (Sync. blackout).

4565 Hz/V failure Fail class F1 to F9

F5

(Shutdown)

PARAMETER LIST 4189340688R EN Page 104 of 222