2.7.4 Speed and running feedback setup

4510 Overspeed 1

No. Setting Range Factory

setting

Description

4511 Overspeed 1 Set point 100 to 150 % 110 % The set point in percentage

4512 Overspeed 1 Timer 0.0 to 100.0 s 5.0 s

relates to nominal RPM.

4513 Overspeed 1 Relay output A Not used (option

dependent)

4514 Overspeed 1 Relay output B Not used (option

dependent)

4515 Overspeed 1 Enable OFF

ON

Not used

Not used

OFF

4516 Overspeed 1 Fail class F1 to F9 F2 (Warning)

4520 Overspeed 2

No. Setting Range Factory

setting

Description

4521 Overspeed 2 Set point 100 to 150 % 120 % The set point in percentage

4522 Overspeed 2 Timer 0.0 to 100.0 s 1.0 s

relates to nominal RPM.

4523 Overspeed 2 Relay output A Not used (option

dependent)

4524 Overspeed 2 Relay output B Not used (option

dependent)

4525 Overspeed 2 Enable OFF

ON

4526 Overspeed 2 Fail class F1 to F9

Not used

Not used

OFF

F5

(Shutdown)

4530 Crank failure

No. Setting Range Factory

setting

Description

4531 Crank failure Set point 1 to 400 RPM 50 RPM If MPU is chosen as the

4532 Crank failure Timer 0.0 to 20.0 s 2.0 s

4533 Crank failure Relay output A Not used (option

dependent)

4534 Crank failure Relay output B Not used (option

dependent)

Not used

Not used

primary running feedback, this

alarm will be raised if the

specified RPM is not reached

before the delay time has

expired.

4535 Crank failure Enable OFF

ON

OFF

4536 Crank failure Fail class F1 to F9 F2 (Warning)

PARAMETER LIST 4189340688R EN Page 103 of 222