2.7.4 Speed and running feedback setup
4510 Overspeed 1
No. Setting Range Factory
setting
Description
4511 Overspeed 1 Set point 100 to 150 % 110 % The set point in percentage
4512 Overspeed 1 Timer 0.0 to 100.0 s 5.0 s
relates to nominal RPM.
4513 Overspeed 1 Relay output A Not used (option
dependent)
4514 Overspeed 1 Relay output B Not used (option
dependent)
4515 Overspeed 1 Enable OFF
ON
Not used
Not used
OFF
4516 Overspeed 1 Fail class F1 to F9 F2 (Warning)
4520 Overspeed 2
No. Setting Range Factory
setting
Description
4521 Overspeed 2 Set point 100 to 150 % 120 % The set point in percentage
4522 Overspeed 2 Timer 0.0 to 100.0 s 1.0 s
relates to nominal RPM.
4523 Overspeed 2 Relay output A Not used (option
dependent)
4524 Overspeed 2 Relay output B Not used (option
dependent)
4525 Overspeed 2 Enable OFF
ON
4526 Overspeed 2 Fail class F1 to F9
Not used
Not used
OFF
F5
(Shutdown)
4530 Crank failure
No. Setting Range Factory
setting
Description
4531 Crank failure Set point 1 to 400 RPM 50 RPM If MPU is chosen as the
4532 Crank failure Timer 0.0 to 20.0 s 2.0 s
4533 Crank failure Relay output A Not used (option
dependent)
4534 Crank failure Relay output B Not used (option
dependent)
Not used
Not used
primary running feedback, this
alarm will be raised if the
specified RPM is not reached
before the delay time has
expired.
4535 Crank failure Enable OFF
ON
OFF
4536 Crank failure Fail class F1 to F9 F2 (Warning)
PARAMETER LIST 4189340688R EN Page 103 of 222