04.01.2023 Views

agc-4-parameter-list-4189340688-uk

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

4480 RMI fuel level 108.1

No. Setting Range Factory

setting

Description

4481 RMI fuel

108.1

4482

RMI fuel

108.1

Set point 0 to 100 % 10 % The multi-input 108 has been

configured as RMI fuel level in

menu 11000.

Timer 0.0 to 999.0 s 10.0 s

4483 RMI fuel

108.1

Relay output A

Not used (option

dependent)

Not used

4484 RMI fuel

108.1

Relay output B

Not used (option

dependent)

Not used

4485 RMI fuel

108.1

Enable

OFF

ON

OFF

4486

RMI fuel

108.1

Fail class F1 to F9 F2 (Warning)

4490 RMI fuel level 108.2

No. Setting Range Factory

setting

Description

4491 RMI fuel

108.2

4492

RMI fuel

108.2

Set point 0 to 100 % 5 % The multi-input 108 has been

configured as RMI fuel level in

menu 11000.

Timer 0.0 to 999.0 s 10.0 s

4493 RMI fuel

108.2

Relay output A

Not used (option

dependent)

Not used

4494 RMI fuel

108.2

Relay output B

Not used (option

dependent)

Not used

4495 RMI fuel

108.2

Enable

OFF

ON

OFF

4496

RMI fuel

108.2

Fail class F1 to F9 F2 (Warning)

4500 Wire fail 108

No. Setting Range Factory

setting

Description

4501 Wire fail 108 Relay output A Not used (option

dependent)

4502 Wire fail 108 Relay output B Not used (option

dependent)

4503 Wire fail 108 Enable OFF

ON

Not used

Not used

OFF

The wire break fault detection

is activated.

4504 Wire fail 108 Fail class F1 to F9 F2 (Warning)

PARAMETER LIST 4189340688R EN Page 102 of 222

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!