04.01.2023 Views

agc-4-parameter-list-4189340688-uk

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

4450 RMI oil 108.2

No. Setting Range Factory

setting

Description

4451 RMI oil 108.2 Set point 0.0 to 145.0 bar 5.0 bar The multi-input 108 has been

4452 RMI oil 108.2 Timer 0.0 to 999.0 s 5.0 s

configured as RMI oil pressure

in menu 11000.

4453 RMI oil 108.2 Relay output A Not used (option

dependent)

Not used Select bar or PSI unit in menu

10970.

4454 RMI oil 108.2 Relay output B Not used (option

dependent)

4455 RMI oil 108.2 Enable OFF

ON

Not used

OFF

4456 RMI oil 108.2 Fail class F1 to F9 F2 (Warning)

4460 RMI water 108.1

No. Setting Range Factory

setting

Description

4461 RMI water

108.1

4462

RMI water

108.1

4463 RMI water

108.1

Set point

Timer

-49 to 482 °C

0.0 to 999.0 s

100 °C

5.0 s

The multi-input 108 has been

configured as RMI water

pressure in menu 11000.

Select C or F unit in menu

10970.

Relay output A Not used (option Not used

dependent)

4464 RMI water

108.1

Relay output B

Not used (option

dependent)

Not used

4465 RMI water

108.1

Enable

OFF

ON

OFF

4466

RMI water

108.1

Fail class F1 to F9 F2 (Warning)

4470 RMI water 108.2

No. Setting Range Factory

setting

Description

4471 RMI water

108.2

4472

RMI water

108.2

4473 RMI water

108.2

Set point

Timer

-49 to 482 °C

0.0 to 999.0 s

110 °C

5.0 s

The multi-input 108 has been

configured as RMI water

pressure in menu 11000.

Select C or F unit in menu

10970.

Relay output A Not used (option Not used

dependent)

4474 RMI water

108.2

Relay output B

Not used (option

dependent)

Not used

4475 RMI water

108.2

Enable

OFF

ON

OFF

4476

RMI water

108.2

Fail class F1 to F9 F2 (Warning)

PARAMETER LIST 4189340688R EN Page 101 of 222

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!