Tekniske Standarder<br />
Komponentliste Bips nr. <strong>61</strong>-<strong>66</strong><br />
<strong>Bilag</strong> 5<br />
1. udgave<br />
Oprettet: April 2012 – Karin Sletskov Henriksen<br />
Godkendt:<br />
Revision: 24092012 JBN<br />
Hospitalsenheden Horsens<br />
Teknisk afdeling
Hospitalsenheden Horsens<br />
Tekniske standarder<br />
Bips nr. 63-<strong>66</strong> - Komponentliste<br />
Indholdsfortegnelse<br />
Materialer og produkter................................................................ 3<br />
Generelle forskrifter, normer m.v. ................................................ 3<br />
63. Lavspænding ................................................................. 4<br />
63.12 Tavler .................................................................................... 4<br />
63.21 Rør ........................................................................................ 4<br />
63.22 Gitterbakker og – stiger............................................................ 4<br />
63.23 Installationskanaler.................................................................. 4<br />
63.51 Anlæg for belysningsanlæg ....................................................... 4<br />
63.52 Anlæg for lysinstallationer......................................................... 7<br />
63.53 Anlæg for nød- og panikbelysning.............................................. 7<br />
63.54 Anlæg for stikkontakter ............................................................ 8<br />
64. Svagstrøm ..................................................................... 8<br />
64.23 Krydsfelter Lene .................................................................... 8<br />
64.<strong>61</strong> Dør- og porttelefonanlæg.......................................................... 11<br />
64.62 Adgangskontrolanlæg............................................................... 11<br />
64.621 Dørautomatik .......................................................................... 11<br />
64.71 Automatiske indbrudsalarmanlæg .............................................. 11<br />
64.81 Brandsikring ........................................................................... 11<br />
64.82 Brandventilation ...................................................................... 12<br />
64.90 CTS kodning ........................................................................... 12<br />
65. Signalanlæg................................................................... 18<br />
65.12 Telefon, trådløs ....................................................................... 18<br />
65.21 Patientkaldeanlæg ................................................................... 18<br />
65.31 Samtaleanlæg ......................................................................... 18<br />
65.41 TV- og radioanlæg ................................................................... 19<br />
65.51 Ur anlæg ................................................................................ 19<br />
<strong>66</strong>. Person- og materialetransport (elevator o.l.)................. 19<br />
00 <strong>Bilag</strong> 5 Komponentliste <strong>61</strong>-<strong>66</strong> El.doc Side 2 af 19
Hospitalsenheden Horsens<br />
Tekniske standarder<br />
Bips nr. 63-<strong>66</strong> - Komponentliste<br />
Materialer og produkter<br />
Dette dokument er til brug for entreprenører og håndværker til opslag af foretrukne produkter i forbindel-<br />
se med ny og ombygninger.<br />
Ved tilbudsafgivelse skal entreprenørerne vedlægge lister med angivelse af de tilbudte komponenter. Hvis<br />
ikke der er angivet noget, skal der leveres det beskrevne. Ved opstart af opgave, skal entreprenøren<br />
kontrollere om alle beskrevne produkter kan skaffes. Hvis ikke, skal entreprenøren finde et tilsvarende<br />
produkt og kontakte TA for godkendelse.<br />
Generelle forskrifter, normer m.v.<br />
Installationer skal opfylde krav til flg. normer og forskrifter i nyeste udg.<br />
63 Lavspænding<br />
DS/EN 285+A2 Sterilisation – Dampautoklaver – Store autokla-<br />
DS/EN 60439-2,-3,-4,-<br />
5+Amds. (Sik)<br />
ver<br />
Lavspændingstavler - Særlige bestemmelser -<br />
Del 2: Kanalskinnesystemer - Del 3: Tavler be-<br />
regnet til at blive installeret på steder, hvor<br />
lægmand har adgang til at betjene dem - Forde-<br />
lingstavler - Del 4: Byggepladstavler (ACS) - Del<br />
5: Tavler beregnet til installation udendørs på<br />
offentlige steder - Kabelfordelingsskabe til kraft-<br />
fordeling i net<br />
DS 700 Kunstig belysning i arbejdslokaler<br />
00 <strong>Bilag</strong> 5 Komponentliste <strong>61</strong>-<strong>66</strong> El.doc Side 3 af 19<br />
2009<br />
2002<br />
DS 703 Retningslinjer for kunstig belysning i sygehuse 1983<br />
DS 704 Belysning. Definitioner 1998<br />
DS/EN 12464-1 Lys og belysning - Belysning ved arbejdspladser<br />
- Del 1: Indendørs arbejdspladser<br />
DS/EN 12<strong>66</strong>5 Lys og belysning - Grundlæggende begreber og<br />
kriterier til beskrivelse af krav til belysning<br />
2011<br />
2011<br />
DS/EN 1838 Belysning. Nødbelysning 1999<br />
DS/EN 50172 Belysningssystemer til nødudgange 2004<br />
DS/IEC 60364-7-710 Elektriske lavspændingsinstallationer – Krav til<br />
64 Svagstrøm<br />
65 Signalanlæg<br />
specielle installationer eller områder - Medicin-<br />
ske områder<br />
Arbejdstilsynets bekendtgørelse nr. 5<strong>61</strong> om ind-<br />
retning af tekniske hjælpemidler (maskindirekti-<br />
vet)<br />
2009
Hospitalsenheden Horsens<br />
Tekniske standarder<br />
Bips nr. 63-<strong>66</strong> - Komponentliste<br />
<strong>66</strong> Person- og materialetransport (elevator o.l.)<br />
63. Lavspænding<br />
63.12 Tavler<br />
63.21 Rør<br />
Fabrikat Cubic, DLK eller efter aftale.<br />
Tavlekomponenter fabrikat skal overholde føl-<br />
gende: Der skal være mulighed for 25 % udvi-<br />
delse<br />
Automatsikringer. Kombineret min. udløse kurve<br />
C og HPFI.<br />
63.22 Gitterbakker og – stiger<br />
63.23 Installationskanaler<br />
CTS tilsluttet bimåler med LON-bus system.<br />
Transientbeskyttelse 8/20µ i hovedtavler og<br />
10/350µ i under-/etagetavler. Skal kunne udskif-<br />
tes uden brug af værktøj og imens der er spæn-<br />
ding på tavle. Fejlsignal overføres til CTS.<br />
CE-mærker samt PVC- og halogenfri.<br />
Fabrikat RM el. lign.<br />
Der anvendes standard bæringer, bøjninger,<br />
beslag, konsoller m.v.<br />
Installationskanal Fabrikat Thorsmann type TEK-XXX<br />
Kabelkanal Fabrikat Thorsmann.<br />
Sengestue-/teknikpanel Fabrikat Fagerhult, Gastech eller Duelco.<br />
63.51 Anlæg for belysningsanlæg<br />
Belysning:<br />
Der skal overalt anvendes armaturer med lysrør<br />
og elektroniske forkoblinger. Flugtsvejsbelysning<br />
med LED er ikke omfattet. I særbelysning, hvor<br />
der stilles specielle krav til belysningen kan der<br />
dispenseres fra kravet, efter godkendes af Tek-<br />
nisk Afdeling.<br />
00 <strong>Bilag</strong> 5 Komponentliste <strong>61</strong>-<strong>66</strong> El.doc Side 4 af 19
Hospitalsenheden Horsens<br />
Tekniske standarder<br />
Bips nr. 63-<strong>66</strong> - Komponentliste<br />
Almenbelysning:<br />
I lokaler med DS-krav om 200 lux i almenbelys-<br />
ningen, må den installerede effekt til almenbe-<br />
lysning ikke overstige 8 W/m 2 . Målet er 5 W/m 2 .<br />
Der ønskes indbygningsarmaturer med en virk-<br />
ningsgrad på ca. 60 % eller bedre, med mindre<br />
andre krav umuliggør dette.<br />
Lystænding:<br />
Sengestuer MAN - 2T (vinduesrække)<br />
Opholds-/venterum PIR-ZONE-OFF<br />
Omklædning PIR<br />
Rengøring PIR<br />
Affaldsrum PIR<br />
Forhal MD-ZONE-UR<br />
Vareindlevering/ bulklager<br />
PIR<br />
Teknikrum Tryk<br />
US 2T-MAN<br />
Kvalitet og udseende som f.eks. Louis Poulsen,<br />
Philips: Modula Wing eller Jacobson: Menlo S2.<br />
Natlys i udvalgte stuer Kvalitet og energiforbrug som Agenlys type ZOC<br />
RS 100PA, E14 10W.<br />
Toilet/bad – loft og væg: Lystænding:<br />
Toilet PIR<br />
Bad PIR<br />
Kvalitet og udseende som:<br />
Loft: Jakobsson Zenit 190H incl. Glas IP44 eller<br />
Louis Poulsen: Beat.<br />
Køkken/skyllerum: Lystænding:<br />
Væg: Jakobsson Kleemann 1x24 W med elektro-<br />
nisk reaktor uden stikkontakt over spejl.<br />
Køkken PIR<br />
Skyllerum PIR<br />
2T-ZONE-MD<br />
Jakobsson Menlo IP44 armatur med opal skærm<br />
eller tilsvarende.<br />
Undersøgelsesrum: Lystænding:<br />
Undersøgelse MAN-2T<br />
Som ”Almenbelysning”.<br />
Undersøgelseslampe som kan overholde følgen-<br />
de:<br />
Min. 55.000 Lux på 1 meters afstand.<br />
Producent: Derungs, for-<br />
handlet af Højager belys-<br />
00 <strong>Bilag</strong> 5 Komponentliste <strong>61</strong>-<strong>66</strong> El.doc Side 5 af 19<br />
ning.<br />
Model: saturn
Hospitalsenheden Horsens<br />
Tekniske standarder<br />
Bips nr. 63-<strong>66</strong> - Komponentliste<br />
Kontorer og møderum:<br />
Pendler over mødebor-<br />
de:<br />
Farvetemperatur på 4.100 Kelvin.<br />
Lystænding:<br />
Kontorer ZONE-MD-2T<br />
Fællesrum, møde mv. ZONE-MAN/MD<br />
Som ”Almenbelysning” – dog tillades nedhængte<br />
armaturer med en del oplys. Maks. 8 W/m 2 skal<br />
overholdes. Målet er 5 W/m 2 .<br />
Anvendes nedhængte armaturer med oplys, skal<br />
armaturvirkningsgraden være højere end 85 %.<br />
Bør kun ophænges i lokaler med hvide vægge og<br />
lofter.<br />
Eksempelvis Højager Belysning: Tycoom Com-<br />
fort, DYP228 med η = 94 %.<br />
Skal bestykkes med kompaktrør eller sparepæ-<br />
rer.<br />
Forventes der mange årlige driftstimer på møde-<br />
rumsbelysningerne, anbefales brug af mere ef-<br />
fektive pendler/lyskilder.<br />
Alternativt kunne der eksempelvis vælges blandt<br />
Jakobssons glaspendler: Stresa, Olla eller Ellip-<br />
sis.<br />
Operationsstuer: Lystænding:<br />
Almen belysning: OP-stuer/skadestuer MAN<br />
med dæmpning<br />
Præparation 2T-MAN<br />
Armatur med samme specielle egenskaber som<br />
Jakobsson Menlo DPC med ramme og glasaf-<br />
skærmning.<br />
Armaturet er specielt designet til operationsstu-<br />
er. Forsynet med dobbeltparabolsk mat gitter for<br />
at undgå ubehagsblænding og generende reflek-<br />
ser i instrumenter.<br />
Desuden er armaturet forsynet med 3 mm hær-<br />
det glas afskærmning.<br />
Depoter: Som ”Almenbelysning”.<br />
Gangarealer og trapper: Lystænding:<br />
I sengestueområde dæmpes belysning i natdrift<br />
som styres af CTS<br />
Områder kun med dagfunktion styre belysning i<br />
natdrift med PIR som styres af CTS<br />
Indgange, gangarealer o. lign. med dagslysind-<br />
00 <strong>Bilag</strong> 5 Komponentliste <strong>61</strong>-<strong>66</strong> El.doc Side 6 af 19
Hospitalsenheden Horsens<br />
Tekniske standarder<br />
Bips nr. 63-<strong>66</strong> - Komponentliste<br />
Under overskabe:<br />
fald LX<br />
Trappe Konstant<br />
Trappeautomater MD<br />
Armaturer som:<br />
Louis Poulsen: DL 3000<br />
Glamox: GCE 24<br />
Thorn: Charlie TC<br />
Solar Luminestra eller lignende med tilsvarende<br />
virkningsgrad.<br />
Udvendig belysning: Lystænding:<br />
Udvendig Signal fra CTS<br />
Væg: Solar Pirat 1x18 W EL eller lignende arma-<br />
turer.<br />
Standere: WEXIÖ<br />
Tunneller: Lystænding:<br />
Tunnel Konstant – 1/3 niveau<br />
PIR/ZONE<br />
Et-rørsarmatur med polycarbonatskærm og HF-<br />
forkobling. Virkningsgraden skal være mindst<br />
75 %.<br />
63.52 Anlæg for lysinstallationer<br />
Alle armaturer udføres med HF-forkobling.<br />
Kabler, ledninger, rør m.v. er PVC- og halogen-<br />
fri.<br />
Kabler som NKT NOPOVIC<br />
Standard afbrydermateriel fabrikat LK.<br />
Ved manuel lys dæmpning anvendes Philips type<br />
LPS for Opus.<br />
PIR følere må maksimalt have et egetforbrug på<br />
1 W.<br />
63.53 Anlæg for nød- og panikbelysning<br />
Fabrikat EL-TEK. Centralt anlæg med enkelt<br />
overvågning, dvs., at hvert enkelt armatur har<br />
sin egen specifikke adresse og ”joker”-funktion.<br />
Ved Joker teknologien kan man forsyne både<br />
flugtvejs- og panikarmaturerne gennem samme<br />
kabel.<br />
Centraltyper: SL-ELS/SV eller SL-CPS/220<br />
00 <strong>Bilag</strong> 5 Komponentliste <strong>61</strong>-<strong>66</strong> El.doc Side 7 af 19
Hospitalsenheden Horsens<br />
Tekniske standarder<br />
Bips nr. 63-<strong>66</strong> - Komponentliste<br />
Henvisningsarmaturer type SL-VRD /230/OV<br />
Panikbelysningsarmatur i nedhængte lofter: type<br />
SN108E-S/SV<br />
63.54 Anlæg for stikkontakter<br />
64. Svagstrøm<br />
Automatik<br />
Kabler, ledninger, rør m.v. er PVC- og halogen-<br />
fri.<br />
Kabler som NKT NOPOVIC.<br />
Standard afbrydermateriel er fabrikat LK.<br />
Stikkontakter i installationspaneler er fabrikat<br />
LK.<br />
Svagstrømskabler ABA/ABDL<br />
64.23 Krydsfelter<br />
Rackskab<br />
Dimensionering af rack-<br />
skab<br />
CEE-stikkontakter planforsænkes, hvor det er<br />
muligt. Der skal være 220 V udtag<br />
Standard afbrydermateriel som fabrikat LK.<br />
IP44 materiel som fabrikat LK.<br />
Manuel lysdæmpning som Philips.<br />
Al styring og regulering skal ske via CTS-anlæg.<br />
Selvstændigt reguleringsudstyr må kun anven-<br />
des efter særlig aftale med bygherren.<br />
CTS<br />
Overfaldsalarmer Grå<br />
Der må være max 90m kabel, kat. 6, mellem<br />
krydsfelt og installationen i væggen – desuden<br />
10m patchkabel (iht. Lovgivning).<br />
Som ? m/afmonterbar sideplade.<br />
Hvert skab skal kunne tilgåes fra 2 sider.<br />
Fra tilgangssiderne skal der være en friplads på<br />
1000 mm.<br />
Opsættes krydsfelt i let støvede områder, skal<br />
der føres et Ø100 ventilationesrør ned i hvert<br />
rackskab.<br />
Bestykning af arbejdsplads:<br />
1 arb. plads svarer til dobbelt rj45 (pc/telefoni)<br />
00 <strong>Bilag</strong> 5 Komponentliste <strong>61</strong>-<strong>66</strong> El.doc Side 8 af 19
Hospitalsenheden Horsens<br />
Tekniske standarder<br />
Bips nr. 63-<strong>66</strong> - Komponentliste<br />
Disponering i rackskab:<br />
Bestykning af kontor/rum:<br />
Antal arb. plads og extra dobbelt rj45<br />
Øvrigt udstyr vurderes af teknisk afdeling<br />
Der skal være mulighed for 20% udbygning af<br />
rackskab.<br />
Det trådløse netværk er et supplement til de<br />
faste installationer men kan ikke erstatte det.<br />
1 2 3 4 5 6 7 8 9 1 0 11 1 2<br />
1 3 14 15 16 17 1 8 1 9 2 0 21 22 23 24<br />
1X<br />
11X<br />
13 X<br />
23X<br />
SYST R PS<br />
STAT UTIL D UP LXS PE ED<br />
2X<br />
12X<br />
14 X<br />
24X<br />
MOD E<br />
1 2 3 4 5 6 7 8 9 1 0 11 1 2<br />
1 3 14 15 16 17 1 8 1 9 2 0 21 22 23 24<br />
SYST R PS<br />
1X<br />
11X<br />
13 X<br />
23X<br />
STAT UTIL D UP LXS PE ED<br />
2X<br />
12X<br />
14 X<br />
24X<br />
MOD E<br />
1 2 3 4 5 6 7 8 9 1 0 11 1 2<br />
1 3 14 15 16 17 1 8 1 9 2 0 21 22 23 24<br />
SYST R PS<br />
1X<br />
11X<br />
13 X<br />
23X<br />
STAT UTIL D UP LXS PE ED<br />
2X<br />
12X<br />
14 X<br />
24X<br />
MOD E<br />
1 2 3 4 5 6 7 8 9 1 0 11 1 2<br />
1 3 14 15 16 17 1 8 1 9 2 0 21 22 23 24<br />
1X<br />
11X<br />
13 X<br />
23X<br />
SYST R PS<br />
STAT UTIL D UP LXS PE ED<br />
2X<br />
12X<br />
14 X<br />
24X<br />
MOD E<br />
1 2<br />
1 2<br />
1 2<br />
Catalyst 2950 S ER IES<br />
Catalyst 2950 S ER IES<br />
1 2<br />
Catalyst 2950 S ER IES<br />
Catalyst 2950 S ER IES<br />
00 <strong>Bilag</strong> 5 Komponentliste <strong>61</strong>-<strong>66</strong> El.doc Side 9 af 19
Hospitalsenheden Horsens<br />
Tekniske standarder<br />
Bips nr. 63-<strong>66</strong> - Komponentliste<br />
Rød og blå struktur:<br />
Principskitse:<br />
Farvekodning:<br />
Rød:<br />
Blå:<br />
Brun:<br />
Lilla:<br />
Orange:<br />
Sort:<br />
Gul:<br />
Grøn:<br />
Pink:<br />
Telefoni.<br />
Grå:<br />
Grøn:<br />
FA N<br />
STATUS<br />
INPUT<br />
100-240 V~<br />
16 A<br />
60/50 Hz<br />
INSTALL<br />
RUN<br />
1<br />
2<br />
3<br />
4<br />
5<br />
6<br />
WS-X6548-GE-TX<br />
1<br />
2<br />
7<br />
8<br />
9<br />
S TATUS<br />
4 8 P O R T<br />
10/10 0/100 0 BASE-T<br />
SWITCHING MODULE PHONE<br />
S TATUS<br />
4 8 P O R T<br />
10/10 0/100 0 BASE-T<br />
SWITCHING MODULE<br />
PHONE<br />
ET HERNET<br />
ET HERNET<br />
INPUT FAN OUTPUT<br />
OK OK FAIL<br />
11<br />
13<br />
1 2<br />
14<br />
Power Supply 1 Power Supply 2<br />
Catalyst 6500 SERIE S<br />
23<br />
2 5<br />
24<br />
26<br />
INPUT<br />
100-240 V~<br />
16 A<br />
60/50 Hz<br />
INSTALL<br />
RUN<br />
3 5<br />
37<br />
36<br />
38<br />
INPUT FAN OUTPUT<br />
OK OK FAIL<br />
4 7<br />
48<br />
1 2<br />
11<br />
9<br />
1 0<br />
1<br />
2<br />
3<br />
4<br />
5<br />
6<br />
7<br />
8<br />
2 4<br />
2 1 3<br />
1 4<br />
1<br />
5<br />
1 6<br />
1 7<br />
1 8<br />
1<br />
9<br />
20<br />
2 1<br />
2 2<br />
3<br />
3 3<br />
3<br />
3<br />
5<br />
3 6<br />
4<br />
2 7<br />
2<br />
2<br />
9<br />
30<br />
3 1<br />
3 2<br />
8<br />
2<br />
5<br />
2 6<br />
4 5<br />
4<br />
4<br />
7<br />
4 8<br />
6<br />
4 1<br />
4<br />
4 3<br />
4 4<br />
2<br />
3 9<br />
4 0<br />
3<br />
7<br />
3 8<br />
PC’ere med DHCP tildelte adresser<br />
PC’ere med DHCP tildelte adresser<br />
Udstyr med fast IP adresse<br />
Udstyr med fast IP adresse<br />
Printere<br />
Internet vlan<br />
Accesspunkter<br />
UPS overvågning<br />
TV<br />
Digitale telefoner, faxe, telefonsvarere<br />
Ascom trådløse telefoner<br />
00 <strong>Bilag</strong> 5 Komponentliste <strong>61</strong>-<strong>66</strong> El.doc Side 10 af 19<br />
FAN<br />
STATUS<br />
INPUT<br />
100-240 V~<br />
16 A<br />
60/50 Hz<br />
INSTALL<br />
RUN<br />
WS-X6548-GE-TX<br />
1<br />
2<br />
1<br />
2<br />
3<br />
4<br />
5<br />
6<br />
WS-X6548-GE-TX<br />
1<br />
2<br />
7<br />
8<br />
9<br />
S TATUS<br />
4 8 P O R T<br />
10/10 0/100 0 BASE-T<br />
SWITCHING MODULE<br />
PHONE<br />
ET HERNET<br />
INPUT FAN OUTPUT<br />
OK OK FAIL<br />
11<br />
13<br />
12<br />
14<br />
11<br />
13<br />
12<br />
14<br />
Power Supply 1 Power Supply 2<br />
Catalyst 6500S ERIES<br />
23<br />
25<br />
24<br />
26<br />
23<br />
25<br />
24<br />
26<br />
INPUT<br />
100-240 V~<br />
16 A<br />
60/50 Hz<br />
INSTALL<br />
RUN<br />
35<br />
37<br />
36<br />
38<br />
35<br />
37<br />
36<br />
38<br />
INPUT FAN OUTPUT<br />
OK OK FAIL<br />
47<br />
48<br />
1 2<br />
11<br />
9<br />
1 0<br />
1<br />
2<br />
3<br />
4<br />
5<br />
6<br />
7<br />
8<br />
2 4<br />
2 1 3<br />
1 4<br />
1<br />
5<br />
1 6<br />
1 7<br />
1 8<br />
1<br />
9<br />
20<br />
2 1<br />
2 2<br />
3<br />
3 3<br />
3<br />
3<br />
5<br />
3 6<br />
4<br />
2 7<br />
2<br />
2<br />
9<br />
30<br />
3 1<br />
3 2<br />
8<br />
2<br />
5<br />
2 6<br />
4 5<br />
4<br />
4<br />
7<br />
4 8<br />
6<br />
4 1<br />
4<br />
4 3<br />
4 4<br />
2<br />
3 9<br />
4 0<br />
1<br />
3<br />
7<br />
3 8<br />
2<br />
11<br />
9<br />
1 0<br />
1<br />
2<br />
3<br />
4<br />
5<br />
6<br />
7<br />
8<br />
2 4<br />
2 1 3<br />
1 4<br />
1<br />
5<br />
1 6<br />
1 7<br />
1 8<br />
1<br />
9<br />
20<br />
2 1<br />
2 2<br />
3<br />
3 3<br />
3<br />
3<br />
5<br />
3 6<br />
4<br />
2 7<br />
2<br />
2<br />
9<br />
30<br />
3 1<br />
3 2<br />
8<br />
2<br />
5<br />
2 6<br />
4 5<br />
4<br />
4<br />
7<br />
4 8<br />
6<br />
4 1<br />
4<br />
4 3<br />
4 4<br />
2<br />
3 9<br />
4 0<br />
3<br />
7<br />
3 8<br />
47<br />
48<br />
Placeres i rød switch<br />
Placeres i blå switch<br />
Placeres i rød switch<br />
Placeres i blå switch<br />
Placeres efter princippet,<br />
ca. hver anden<br />
Der defineres switchporte<br />
til internet<br />
Der defineres switchporte<br />
til AP’er
Hospitalsenheden Horsens<br />
Tekniske standarder<br />
Bips nr. 63-<strong>66</strong> - Komponentliste<br />
Bygherre leverance Et stk telefonlinie<br />
Kabling til 2 uafhængige serverrum via forskelli-<br />
ge føringsveje<br />
Det aktive udstyr Ansvarlig er Regionens IT drift.<br />
64.<strong>61</strong> Dør- og porttelefonanlæg<br />
64.62 Adgangskontrolanlæg<br />
Aftales med brugerne<br />
Evt. skal signal gives til patientkaldeanlæg.<br />
Gruppe 2: Låse fabrik Ruko, EL582, låsespænding 24 VDC.<br />
64.621 Dørautomatik<br />
Tastatur Conlan CT2000<br />
Strømforsyning type 48813<br />
Switchmode DC12 PSU12<br />
Komponenter forhandles bl.a. af Louis Poulsen.<br />
Dørblad monteret: Som record DAF 127 standard kabinet<br />
Som record DAF 127-2 åbning til dobbeltdør<br />
Snoretræk kontak Som type XCK-M Telemecanique el. tilsvarende<br />
Albuekontakt: Som Besam 600051 el. tilsvarende<br />
Fodkontakt Som BEA PBSP kvadratisk fodtryk m/sort sokkel<br />
fra RECORD el. tilsvarende.<br />
Fås også som trådløs udgave.<br />
Arbejdsafbryder: Som Fuga nøgleafbryder el. tilsvarende<br />
64.71 Automatiske indbrudsalarmanlæg<br />
Tyvericentral RS224 med 8 alarmzoner inkl. alarmsender.<br />
Elektronisk sirene AS270<br />
Passiv infrarød detekto-<br />
rer<br />
Åbningskontakt DC120.<br />
EV135, 90 gr. 12 m.<br />
Nøgleboks Danboks sabotagesikret.<br />
64.81 Brandsikring<br />
ABA-anlæg: Brandcentral fabr. Nittan type Alfa 2001.<br />
Akustisk alarmgiver fabr. Alarm System type<br />
V.24H/Opus.<br />
00 <strong>Bilag</strong> 5 Komponentliste <strong>61</strong>-<strong>66</strong> El.doc Side 11 af 19
Hospitalsenheden Horsens<br />
Tekniske standarder<br />
Bips nr. 63-<strong>66</strong> - Komponentliste<br />
Nøgleboks type Danboks.<br />
ABDL-anlæg: ABDL-central fabr. Alarm System type 4000.<br />
64.82 Brandventilation<br />
64.90 CTS kodning<br />
Optiske- eller iondetektor fabr. Alarm System<br />
type S65.<br />
Der skal fortrins anvendes Dorma friløbsdørluk-<br />
ker type TS73 EMF eller lignende med samme<br />
funktion.<br />
Fabr. Sikkerhedsteknik A/S<br />
Central type ST-ES 251, inkl. batteriback-up.<br />
Ved 2 motorer anvendes central type ST-ES 601<br />
eller ST-ESM6/1 afhængig af køretid og ampere-<br />
forbrug.<br />
Røglemstryk type ST-HE 075, farve grå, med<br />
tekst røglem.<br />
Ved facadevinduer anvendes kædemotor type<br />
ST-EA-K */*. Ved bredde vinduer monteres eks-<br />
tra motorer.<br />
Ved ovenlysvinduer anvendes tandstangsmotor<br />
type ST-SZ_24/800/*. Ved bredde ovenlys mon-<br />
teres ekstra motorer eller medløbere.<br />
Bygn Etage Rum Anlæg Komponent Index<br />
XX XX XX XXXX XXXXX XX<br />
Anlæg<br />
ABA automatisk brandalarm anlæg<br />
ADK adgangskontrol<br />
ALA alarmanlæg<br />
COL køleanlæg<br />
DIV diverse anlæg<br />
EL elanlæg<br />
ELE elevator<br />
ELT el-tracing<br />
ESC escalator<br />
FC fan coil<br />
FJV fjernvarme<br />
00 <strong>Bilag</strong> 5 Komponentliste <strong>61</strong>-<strong>66</strong> El.doc Side 12 af 19
Hospitalsenheden Horsens<br />
Tekniske standarder<br />
Bips nr. 63-<strong>66</strong> - Komponentliste<br />
IND indblæsningsanlæg<br />
KED kedelanlæg<br />
KOM kompressoranlæg<br />
KON kondensatanlæg<br />
KV koldt brugsvand<br />
LYS lysstyring<br />
PUM pumpebrønd<br />
RAD radiatoranlæg<br />
SOL solafskærmning<br />
SPR sprinkleranlæg<br />
TRL trykluftanlæg<br />
UDS udsugningsanlæg<br />
VAP varmepumpe<br />
VAR varmeanlæg (generelt)<br />
VEN ventilationsanlæg<br />
VES vejrstation<br />
VGV varmegenvinding<br />
VIN vinduesanlæg<br />
VV varmeveksler<br />
VVB varmtvandsbeholder / varmt brugsvand<br />
Komponenter:<br />
Temperaturføler/termostat<br />
TA temperaturalarm<br />
TBH temperatur beholder<br />
TBI termostat brand indblæsning<br />
TBU termostat brand udsugning<br />
TF temperatur fremløb<br />
TFI termostat frost indblæsning<br />
TI temperatur indblæsning<br />
TR temperatur retur<br />
TRC temperatur recirkulation<br />
TRU temperatur rum<br />
TU temperatur udsugning<br />
TUD temperatur ude<br />
00 <strong>Bilag</strong> 5 Komponentliste <strong>61</strong>-<strong>66</strong> El.doc Side 13 af 19
Hospitalsenheden Horsens<br />
Tekniske standarder<br />
Bips nr. 63-<strong>66</strong> - Komponentliste<br />
Fugtføler/hygrostat<br />
HA fugtalarm<br />
HI relativ fugt indblæsning<br />
HRU relativ fugt rum<br />
HU relativ fugt udsugning<br />
HUD relativ fugt ude<br />
Vejrstation<br />
LUX lys intensitet (lux)<br />
RD Regn detektor<br />
SI Sol intensitet vandret (W/m2)<br />
VH vindhastighed<br />
VR vindretning<br />
Niveauføler/-indikator<br />
LA niveaualarm / pumpebrøndalarm<br />
LI niveauføler/-indikator<br />
Differenspressostat / differenstryktransmitter<br />
PDA diff. tryk over varmeanlæg<br />
PDI diff. tryk indblæs (f.eks. ventilatorvagt)<br />
PDP diff. tryk pumpe<br />
PDR diff. tryk rum<br />
PDU diff. tryk udsugning (f.eks. ventilatorvagt)<br />
PDV diff. tryk genvindingsveksler (tilisningsvagt)<br />
PFI diff. tryk filter indblæsning<br />
PFU diff. tryk filter udsugning<br />
Pressostat /tryktransmitter<br />
PA trykalarm<br />
PT tryk (generelt)<br />
PTI tryk indblæsning<br />
PTU tryk udsugning<br />
Motorventiler<br />
00 <strong>Bilag</strong> 5 Komponentliste <strong>61</strong>-<strong>66</strong> El.doc Side 14 af 19
Hospitalsenheden Horsens<br />
Tekniske standarder<br />
Bips nr. 63-<strong>66</strong> - Komponentliste<br />
MVB motorventil befugtning<br />
MVD motorventil damp<br />
MVG motorventil genvinding<br />
MVK motorventil køling<br />
MVV motorventil varme<br />
Magnetventiler<br />
MNB magnetventil befugtning<br />
MND magnetventil damp<br />
MNG magnetventil genvinding<br />
MNK magnetventil køling<br />
MNV magnetventil varme<br />
Spjæld<br />
SBR brandspjæld (overvågning)<br />
SMB spjældmotor bypass<br />
SMG spjældmotor genvinding<br />
SMI spjældmotor indblæsning<br />
SMR spjældmotor recirkulation<br />
SMU spjældmotor udsugning<br />
SVU volustat<br />
Rotorveksler m.m.<br />
RV rotorveksler<br />
Pumper<br />
PB pumpe varmt brugsvand<br />
PG pumpe genvinding<br />
PGR pumpe (grundvand / spildevand)<br />
PK pumpe køling<br />
PKO pumpe kondensat<br />
PV pumpe varme<br />
Ventilatorer<br />
VE ventilationsanlæg fællessignal<br />
VI ventilator indblæsning<br />
00 <strong>Bilag</strong> 5 Komponentliste <strong>61</strong>-<strong>66</strong> El.doc Side 15 af 19
Hospitalsenheden Horsens<br />
Tekniske standarder<br />
Bips nr. 63-<strong>66</strong> - Komponentliste<br />
VU ventilator udsugning<br />
Flow<br />
FA flowalarm<br />
FC flowtransmitter/flowswitch<br />
Forbrugsmålere<br />
COM energimåling (køling)<br />
EM energimåling (el-måler)<br />
EMT el-måler (tarifsignaler)<br />
FM flowmåling (generelt)<br />
GM flowmåling gas<br />
KOM flowmåling kondensat<br />
KVM flowmåling koldt vand<br />
QM energimåling (varme)<br />
VVM flowmåling varmt vand<br />
Diverse alarmer<br />
AL andre alarmer (fællesalarm)<br />
CO CO måling<br />
CO2 CO2 måling<br />
GAS gas måling<br />
ID ion måling<br />
NH3 NH3 måling<br />
NK elevatoralarm<br />
SMO røgmelder<br />
Diverse komponenter<br />
BD dampbefugter<br />
DF driftfrigivelse<br />
DK dørkontakt<br />
DT Lokal betjening (f.eks. timertryk)<br />
FOM funktionsomskifter<br />
KE el (kommando til el-varme, el-tracing m.m.)<br />
KG gardiner/persienner (kommando til gardi-<br />
ner/persienner.)<br />
00 <strong>Bilag</strong> 5 Komponentliste <strong>61</strong>-<strong>66</strong> El.doc Side 16 af 19
Hospitalsenheden Horsens<br />
Tekniske standarder<br />
Bips nr. 63-<strong>66</strong> - Komponentliste<br />
KK køleanlæg (kommando til køleanlæg)<br />
KL lys / indikeringslys (kommando til lys)<br />
LK Luftkvalitet<br />
POT Lokal betjening set punkt. (potentiometer)<br />
PIR PIR føler<br />
Nummerering af komponenter sker i processens<br />
retning.<br />
Hvis et anlæg er delt i zoner tilstræbes følgende<br />
komponentnummerering<br />
Hovedanlæg 01 – 09<br />
Zone 1 11 – 19<br />
Zone 2 21 - 29<br />
hvis punkt er overordnet eller fælles for flere ens<br />
komponenter kan det<br />
eventuelt nummereres 00 - eller som eksempler-<br />
ne herunder<br />
TBIU fælles indgang for brandtermostat i indblæsning<br />
og udsugning<br />
PFIU fælles indgang for filter pressostater i indblæs-<br />
Index<br />
ning og udsugning<br />
_K kommando (start/stop signal til ventila-<br />
tor/pumpe/m.m.)<br />
_D driftsignal/tilbagemelding (ventilator/pumpe/<br />
m.m.)<br />
_T termofejl (ventilator/pumpe/m.m.)<br />
_F fejlsignal (ventilator/pumpe/m.m.)<br />
_S styresignal (fx 0-10V)<br />
_L lav hastighed<br />
_H høj hastighed<br />
_N natsænkning<br />
_P analog stillingsindikering (fx % fra frekvensom-<br />
former)<br />
_HZ tilbagemelding fra frekvensomformer i Hz<br />
00 <strong>Bilag</strong> 5 Komponentliste <strong>61</strong>-<strong>66</strong> El.doc Side 17 af 19
Hospitalsenheden Horsens<br />
Tekniske standarder<br />
Bips nr. 63-<strong>66</strong> - Komponentliste<br />
65. Signalanlæg<br />
65.12 Telefon, trådløs<br />
Ascom<br />
65.21 Patientkaldeanlæg<br />
Som fabrikat Flex-call (før nursefinder, CD200), Lindpro A/S eller Ascom. Aftales med Teknisk afdeling.<br />
Med efterfølgende komponenter:<br />
Hovedapparat<br />
Underapparat med display<br />
Underapparat uden display<br />
Trækkontakt<br />
Jackfatning<br />
Hjertestopstryk<br />
Gangdisplay<br />
Rumlampe 3 felter<br />
Berolampe 1 felt<br />
Tuner<br />
Sengebetjeningsenhed<br />
Betjeningsenhed for rumradio<br />
Personsøger<br />
Centraludstyr<br />
Strømforsyning<br />
Software for PC udstyr<br />
Software for log<br />
Software for personsøger<br />
Telekabler XXx2x0.6 PTS<br />
65.31 Samtaleanlæg<br />
Samtaleanlæg i elevatorer:<br />
Betjeningskomponenter, som indbyg-<br />
ges/indfældes i sengestuepaneler, skal være som<br />
Gastech, Duelco eller Fagerhult afbryder- eller<br />
stikkontaktformat i standard farve.<br />
Til værelse-/ afstillingsapparat anvendes fabr.<br />
Thorsmann, el. nr. 91.20.158.008.<br />
Materiale Beskrivelse Placering Leverandør<br />
00 <strong>Bilag</strong> 5 Komponentliste <strong>61</strong>-<strong>66</strong> El.doc Side 18 af 19
Hospitalsenheden Horsens<br />
Tekniske standarder<br />
Bips nr. 63-<strong>66</strong> - Komponentliste<br />
Samtaleanlægsapparat En knaps kald I elevatorer ASCOM<br />
Krydsfelt LSA+ Med skillemulighed ASCOM<br />
Kabel 0,6 mm parsnoet<br />
65.41 TV- og radioanlæg<br />
Fællesantenneanlægget<br />
indeholder følgende sta-<br />
tioner:<br />
65.51 Ur anlæg<br />
Forstærker, fordeler m.v. fabrikat Arcodan.<br />
R/TV-stikkontakt fabrikat LK.<br />
DR1<br />
DR2<br />
TV2<br />
TV3<br />
TV3+<br />
TV<br />
Kanal Placering<br />
TV2 NEWS<br />
Discovery<br />
P3<br />
RADIO<br />
Kanal Placering<br />
P4 - Trekant<br />
Radio Horsens<br />
Centralt ur anlæg Fabrikat Eltime Ø300 mm med stregvisning.<br />
<strong>66</strong>. Person- og materialetransport (elevator o.l.)<br />
Fabrikat ThyssenKrupp. Loftbeklædningen udføres med melaminplade i<br />
farven hvid, der afsluttes med en glat frise langs<br />
væggene.<br />
00 <strong>Bilag</strong> 5 Komponentliste <strong>61</strong>-<strong>66</strong> El.doc Side 19 af 19